| 2013-03-25 13:31:38 | 2026 PONCE DELEON AVENUE |
| | PERMIT #13030498 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | **NOTE: THIS IS A CHANGE OF OCCUPANCY FROM RESIDENTIAL |
| | TO COMMERCIAL (BUSINESS).** |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR |
| | AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL |
| | HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS |
| | PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL |
| | BE PROVIDED. |
| | |
| | ANY AREA (STORAGE) HAVING A DEGREE OF HAZARD GREATER |
| | THAN NORMAL TO THE GENERAL OCCUPANCY (BUSINESS) OF THE |
| | BUILDING, SHALL BE SEPARATED FROM NON-STORAGE AREAS |
| | WITH A 1-HOUR FIRE-RATED BARRIER OR BE PROTECTED WITH |
| | AN AUTOMATIC SPRINKLER SYSTEM. DOORS SHALL BE SELF |
| | CLOSING, POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST |
| | 45-MINUTES PER SECTION 8.7 OF NFPA 101. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| | CONTRAST THE BACKGROUND (REFERENCE: SECTION 10.12.1.2 |
| | OF THE FLORIDA FIRE PREVENTION CODE ? NFPA 1). |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE LETTER "R" DESIGNATION |
| | PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE |
| | CODE 69A-60.0081. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL |
| | OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING |
| | OPERATION. THE RELEASING MECHANISM SHALL HAVE AN |
| | OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED |
| | UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE |
| | SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND |
| | SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR |
| | TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9 |
| | OF NFPA 101 FLORIDA EDITION 2007. |
| | |
| | ANY THUMB-TURN STYLE LOCKS TO BE EQUIPPED WITH A |
| | LOCK/UNLOCK INDICATOR. |
| | |
| | STORAGE ROOM: EACH FIRE RATED BARRIER SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE |
| | AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | REFERENCE SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION |
| | CODE ? NFPA 101 |
| | |
| | SHEET LS-1 INDICATES THE BUILDING IS PROTECTED BY FIRE |
| | SPRINKLERS AND A FIRE ALARM SYSTEM. PLEASE CONFIRM THIS |
| | IS ACCURATE. |
| | |