Date Text
2013-03-26 13:38:09***PROVISO***
 THE RESTROOMS AND ACCESSIBLE STALLS SHOWN ON A6.0 ARE
 ALL REQUIRED TO BE A MINIMUM OF 7'-1" WIDE TO ACHIEVE
 THE REQUIRED 60" CLEAR SPACE FOR THE WATER CLOSET.
 FBC ACCESSIBILITY CODE 2010 604.3.1 SIZE. CLEARANCE
 AROUND A WATER CLOSET SHALL BE 60 INCHES (1525 MM)
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL
 NOT BE PERMITTED IN THE 60" SPACE.
 PLEASE ALSO SEE FIGURE 604.8.1.6
  