Plan Review Notes
Plan Review Notes For Permit 13030497
Permit Number 13030497
Review Stop M
Sequence Number 1
Notes
Date Text
2013-04-01 13:32:17PASS PROVISO
 1) REFER TO SECTION 601.4 BALANCED RETURN AIR.
 2010 FBC (M)
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS.
 FOR FRESH AIR AND EXHAUST 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved