| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: ALL CONSTRUCTION AND DEMOLITION WORK SHALL |
| | CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH AND |
| | CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE |
| | DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED |
| | EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION |
| | AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE |
| | SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING |
| | MATERIALS SHALL BE PROVIDED. |
| | |
| | SHEET A1.0: UPDATE THE CODE LIST TO REFERENCE THE 2010 |
| | EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| | CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| | WITH FLORIDA AMENDMENTS. |
| | |
| | SHEET A1.0: FIRE LANES SHALL HAVE AN UNOBSTRUCTED WIDTH |
| | OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL |
| | CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES PER SECTION |
| | 18.2.3.4.1.1 OF THE FLORIDA FIRE PREVENTION CODE - NFPA |
| | 1 UNIFORM FIRE CODE. |
| | |
| | SHEET A1.0: THE EXISTING UNMARKED FIRE LANE IS |
| | CONTINUOUSLY ENCROACHED UPON BY PARKED VEHICLES. FIRE |
| | LANES SHALL BE MARKED WITH PAINTED STRIPING AND |
| | FREESTANDING SIGNS READING, "FIRE LANE - NO PARKING BY |
| | ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18" |
| | WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL BE A |
| | MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE |
| | SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW |
| | AND BE SPACED A MAXIMUM OF 60 FEET APART. FLORIDA FIRE |
| | PREVENTION CODE SECTION 18.2.3.5.3. |
| | |
| | SHEET A1.1: PLEASE INDICATE THE FIRE RESISTANCE RATINGS |
| | OF NEW/EXISTING FIRE BARRIERS. |
| | |
| | SHEET A1.1: THE SECOND FLOOR BREAK ROOM AREA APPEARS TO |
| | BE APPROXIMATELY 900 SQ.FT. WITH AN OCCUPANT LOAD OF 60 |
| | PERSON (15 SQ.FT. PER PERSON) RESULTING IN AN ASSEMBLY |
| | OCCUPANCY. |
| | |
| | SHEET A1.1: THE SECOND FLOOR STORAGE ROOMS HAVE |
| | UNPROTECTED VERTICAL OPENINGS BETWEEN THE FIRST AND |
| | SECOND FLOOR. THESE OPENINGS ARE NOT PERMITTED TO BE |
| | UNPROTECTED PER SECTION 42.3.1(2) OF NFPA 101 (2009 |
| | EDITION WITH FLORIDA AMENDMENTS). |
| | |
| | SHEET A1.1: SHEET A1.0 INDICATES A SEPARATED USE |
| | DESIGN; HOWEVER, THREE REAR EXITS APPEAR TO LEAD |
| | INTO/THROUGH THE INDUSTRIAL OCCUPANCY (SERVICE BAYS). |
| | DOORS AND WINDOWS APPEAR TO BE UNRATED/UNPROTECTED |
| | ALONG THE REAR WALL OF THE BUILDING. |
| | |
| | SHEET A2.1: THE AREA OF REFUGE SHALL COMPLY WITH ALL |
| | REQUIREMENTS OF 7.2.12.2 AND 7.2.12.3 OF NFPA 101 (2009 |
| | EDITION WITH FLORIDA AMENDMENTS). |
| | |