Plan Review Notes
Plan Review Notes For Permit 13030497
Permit Number 13030497
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-03-21 14:21:002707 OKEECHOBEE BOULEVARD
 PERMIT #13030497
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: ALL CONSTRUCTION AND DEMOLITION WORK SHALL
 CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH AND
 CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 SHEET A1.0: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET A1.0: FIRE LANES SHALL HAVE AN UNOBSTRUCTED WIDTH
 OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES PER SECTION
 18.2.3.4.1.1 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1 UNIFORM FIRE CODE.
  
 SHEET A1.0: THE EXISTING UNMARKED FIRE LANE IS
 CONTINUOUSLY ENCROACHED UPON BY PARKED VEHICLES. FIRE
 LANES SHALL BE MARKED WITH PAINTED STRIPING AND
 FREESTANDING SIGNS READING, "FIRE LANE - NO PARKING BY
 ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18"
 WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL BE A
 MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE
 SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW
 AND BE SPACED A MAXIMUM OF 60 FEET APART. FLORIDA FIRE
 PREVENTION CODE SECTION 18.2.3.5.3.
  
 SHEET A1.1: PLEASE INDICATE THE FIRE RESISTANCE RATINGS
 OF NEW/EXISTING FIRE BARRIERS.
  
 SHEET A1.1: THE SECOND FLOOR BREAK ROOM AREA APPEARS TO
 BE APPROXIMATELY 900 SQ.FT. WITH AN OCCUPANT LOAD OF 60
 PERSON (15 SQ.FT. PER PERSON) RESULTING IN AN ASSEMBLY
 OCCUPANCY.
  
 SHEET A1.1: THE SECOND FLOOR STORAGE ROOMS HAVE
 UNPROTECTED VERTICAL OPENINGS BETWEEN THE FIRST AND
 SECOND FLOOR. THESE OPENINGS ARE NOT PERMITTED TO BE
 UNPROTECTED PER SECTION 42.3.1(2) OF NFPA 101 (2009
 EDITION WITH FLORIDA AMENDMENTS).
  
 SHEET A1.1: SHEET A1.0 INDICATES A SEPARATED USE
 DESIGN; HOWEVER, THREE REAR EXITS APPEAR TO LEAD
 INTO/THROUGH THE INDUSTRIAL OCCUPANCY (SERVICE BAYS).
 DOORS AND WINDOWS APPEAR TO BE UNRATED/UNPROTECTED
 ALONG THE REAR WALL OF THE BUILDING.
  
 SHEET A2.1: THE AREA OF REFUGE SHALL COMPLY WITH ALL
 REQUIREMENTS OF 7.2.12.2 AND 7.2.12.3 OF NFPA 101 (2009
 EDITION WITH FLORIDA AMENDMENTS).
  