| Plan Review Notes For Permit 13030468 |
| Permit Number |
13030468 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-04-02 14:09:51 | 13030468 | | | 501 FERN ST #C | | | SHELL CONSTRUCTION FOR FUTURE TENANTS | | | | | | THE RESPONSE SUBMITTED FOR 2ND REVIEW IS NOT AS EARLIER | | | DISCUSSED. THE SUGGESTION WAS TO PROVIDE A TEMPORARY | | | ELECTRIC SERVICE TO BEGIN CONSTRUCTION PENDING A FOLLOW | | | UP SUBMITTAL WHICH ADDRESSES THE NEC CODE REQUIREMENT | | | FOR A SINGLE POINT OF SERVICE. THE PLANS STILL SHOW | | | MULTIPLE ELECTRICAL SERVICES. | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | THE ELECTRICAL SERVICE MAINS MUST BE GROUPED IN ONE | | | LOCATION. YOUR REQUEST FOR MULTIPLE SERVICE POINTS HAS | | | BEEN DENIED. THIS STRUCTURE IS NOT SUFFICIENTLY LARGE | | | NOR DOES IT EXHIBIT ANY SPECIAL CONDITIONS WHICH WOULD | | | WARRANT THE SPECIAL PERMISSION REQUESTED FOR MULTIPLE | | | ELECTRICAL SERVICES. THE PRINCIPAL SAFETY RULE FOR | | | ELECTRICAL SERVICES REQUIRES A BUILDING OR STRUCTURE TO | | | HAVE ONE POINT OF SERVICE. NEC 230.2, 230.71, 230.72 | | | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. NEC 250.94 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|