| 2013-03-22 18:52:31 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PROPOSED DESIGN PRESSURES ARE TOO LOW. FOR INSTANCE | | | - OPENING AT BEDROOM 53X54, PROPOSED DP IS +-39.9, | | | ASCE7 REQUIRES A DESIGN PRESSURE OF +46.65/-50.78. | | | | | | EITHER PROVIDE ENGINEERING FOR THE DESIGN PRESSURES | | | PROPOSED OR REVISE FLOOR PLAN AND PRODUCT APPROVAL | | | MARKINGS TO COMPLY WITH WORST CASE FOR THIS JOB WHICH | | | IS +46.65/-50.78 IF ALL OPENINGS ARE IN ZONE 4. | | | |
|