| Plan Review Notes For Permit 13030406 |
| Permit Number |
13030406 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-26 14:12:15 | 13030406 | | | 700 S. ROSEMARY AVE #104 | | | L.A. FITNESS (PRELIMINARY PLAN) | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. | | | NEC 110.22, 110.16, 110.22 | | | | | | GROUND FAULT PROTECTION EQUIPMENT (GFPE) IS REQUIRED | | | FOR THE NEW ELECTRIC SERVICE. NEC 230.95 | | | | | | INDICATE THE FAULT CURRENT INTERRUPTING RATING REQUIRED | | | FOR THE ELECTRICAL SERVICE EQUIPMENT. NEC 110.9 | | | | | | | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|