| 2013-03-25 11:29:59 | BUILDING PLAN REVIEW |
| | PERMIT: 13030406 |
| | ADD: 700 S ROSEMARY # 104 |
| | CONT: CHANDLIER CONSTRUCTION |
| | CONTACT:JOHN CHANDLIER |
| | TEL: (561)791-6934 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE THIS PERMIT IS WORK TO BE ACCOMPLISHED UNDER THE |
| | LANDLORD ONLY BUT THERE ARE ISSUES TO BE WORKED OUT BY |
| | BOTH THE TENANT AND LANDLORDAND TO WHICH THE LANDLORD |
| | OR TENANT WILL TAKE RESPONSIBILITY. |
| | |
| | 1A) SHEET A-1.0 INDICATES THAT THIS TENANT SPACE IS NOT |
| | CHANGE OF OCCUPANCY. BARNES & NOBLE OCCUPIED THIS SPACE |
| | A MERCANTILE OCCUPANCY. LA FITNESS IS PROPOSING TO |
| | BECOME THE NEW TENANT, A A-3 OCCUPANCY. THE DESIGNER OF |
| | RECORD WILL NEED TO REVIEW THE 2010 EXISTING BUILDING |
| | CODE 901.3.1 FOR BUILDINGS THAT ARE UNDER GOING A |
| | PARTIAL CHANGE OF OCCUPANCY, SECTION 912 WILL APPLY. |
| | |
| | 1B) SHEET A1-0 NOTE # 16 REFERENCE MINIMUM EXIT AISLES |
| | OR CORRIDORS AND CODE REFERENCE 1017.2 FOR AISLES FOR |
| | BUSINESS & MERCANTILE, THIS IS AN A-3 OCCUPANCY. PLEASE |
| | CORECT. |
| | |
| | 1C) 1B) SHEET A1-0 NOTE # 17 REFERENCE THE MINIMUM |
| | NUMBER OF EXITS REQUIRED AND REFERNCES TABLE 1019.1, NO |
| | SUCH TABLE, SECTION 1019.1 IS FOR EGRESS BALCONIES. |
| | |
| | 1D) 1B) SHEET A1-0 NOTE # 18 REFERENCES THE NUMBER OF |
| | EXITS PROVIDED AS THREE ACTUALLY ONLY TWO, THE FRONT |
| | AND THE BACK, THE TWO VERTICAL EXITS DROP INTO THE SAME |
| | EXIT PASSAGE WAY. |
| | |
| | 1E) SHEET A1-0 NOTE # 19 REFERENCES MAXIMUM PATH OF |
| | TRAVEL, AND SECTION 1025.8 WHICH DEALS WITH HORIZONTAL |
| | EXITS. |
| | |
| | 1F) 1B) SHEET A1-0 NOTE # 20 REFERENCES MAXIMUM DEAD |
| | ENDS AND REFENECES SECTION # 1017 BUT IS AISLES. |
| | |
| | 2A) THE DESIGNER OF RECORD SHALL ELECT TO DESSIGN THIS |
| | TENANT SPACE UNDER EITHER SECTION: |
| | 912.1.1.1 CHANGE OF OCCUPANCY CLASSIFICATION WITHOUT |
| | SEPARATION. |
| | 912.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH |
| | SEPARATION. |
| | |
| | 3) ) 2010 EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR |
| | CHANGE TO HIGHER HAZARD CATEGORY. |
| | WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| | HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| | 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 4) THE MONUMENTAL STAIR IS NOW AN ISSUE (A-3 OCCUPANCY) |
| | WHERE IT WAS NOT UNDER THE MERCANTILE OCCUPANCY. THE |
| | EXCEPTION FOR MONUMENTAL STAIRS IS FOUND UNDER 708.2 |
| | EXCEPTION # 7, THE MONUMENTAL STAIR NOT REQUIRED TO BE |
| | PART OF THE MEANS OF EGRESS BECAUSE THERE WERE 2 |
| | VERTICAL EXITS TO THE 2ND FLOOR. |
| | |
| | THE 2010 FBC-B SECTION 1028.2 REQUIRES 50 % OF THE |
| | TOTAL OCCUPANTS TO EXIT THROUGH THE MAIN EXIT. 1028.3 |
| | ASSEMBLY OTHER EXITS. EACH LEVEL OF AN ASSEMBLY |
| | OCCUPANCY SHALL HAVE ACCESS TO A MAIN EXIT AND SHALL BE |
| | PROVIDED WITH ADDITIONAL EXITS OF SUFFICIENT WIDTH TO |
| | ACCOMMODATE ONE-HALF OF THE TOTAL OCCUPANT LOAD SERVED |
| | BY THAT LEVEL. SUCH ADDITIONAL EXITS SHALL BE LOCATED |
| | AS FAR FROM THE MAIN ENTRANCE/EXIT AS PRACTICABLE. SUCH |
| | EXITS SHALL BE ACCESSIBLE FROM A CROSS AISLE OR A SIDE |
| | AISLE. PLEASE PROVIDE CODE COMPLIANCE. |
| | |
| | IF THE MONUMENTAL STAIR WAS ENCLOSED ON BOTH FLOORS |
| | WITH A ONE HOUR RATED ENCLOSURE IT WOULD THEN BECOME A |
| | CODE COMPLIANT SET OF EXIT STAIRS, THEY WOULD NOT BE |
| | REQUIRED TO GO TO THE EXTERIOR OF THE BUILDING SINCE |
| | THE 2 VERTICAL EXITS WOULD MEET THAT REQUIREMENT. DOORS |
| | COULD BE LEFT IN THE OPEN POSITION IF THEY WERE TIED TO |
| | MAG LOCKS AND THE FIRE ALARM. |
| | |
| | 5) THE LIFE SAFETY PLANS HAVE SERIOUS PROBLEMS SINCE |
| | THE MONUMETAL STAIRS CAN NOT BE USED FOR EXITING AND |
| | SINCE THE 2ND FLOOR OCCUPANT LOAD IS AT 500 OCCUPANTS, |
| | NEITHER THE STAIRS NOR THE DOORS AT THE BACK OF THE |
| | BUILDING WILL HANDLE THESE OCCUPANT LOADS. THE DESIGNER |
| | IS TAKING A 36 INCH DOOR AND STATING 180 OCCUPANTS CAN |
| | EXIT THIS OPENING, WHEREAS THE CLEAR OPENING IS CLOSER |
| | TO 34 INCHES AND ONLY 170 OCCUPANTS CAN EXIT. FOR A |
| | PAIR OF DOUBLE DOORS 340 OCCUPANTS. THE BACK OF HOUSE |
| | SEERVICE CORRIDOR IS ALSO CONSIDERED A EXIT PASSAGEWAY |
| | SINCE IT IS A CONTINUATION OF THE VERTICAL EXIT. MANY |
| | OF THE DOORS IN THIS EXIT PASSAGEWAY DOORWAYS ARE NOT |
| | WIDE ENOUGH FOR THE NEW ASSEMBLY OCCUPANCIES THAT NOW |
| | EXIST. FOR EXAMPLE TO THE SOUTH THE SPACE WAS |
| | ORIGINALLY DESIGN FOR MERCANTILE OCCUPANCY, THIS IS NOW |
| | GOING TO BE A RESTRAUNT WITH DOUBLE THE OCCUPANT LOAD |
| | OF HOW THE EXIT PASSAGE WAY WAS DESIGNED. THE SAME HOLD |
| | TRUE JUST TO THE NORTH, A SECOND FLOOR NIGHTCLUB AND |
| | THE SECONDARY EXIT THAT LEADS TO THE EXIT STAIRS. |
| | PLEASE PROVIDE THE OCCUPANT LOADS THAT WILL SHARE THE |
| | EXITING FOR THIS COMMON EXIT PASSAGE WAY. PLEASE NOTE |
| | PART OF THE EXIT DISCHARGE A 4 FOOT WIDE SIDEWALK |
| | AND STAIRS., THE STAIRS WILL ONLY ALLOW FOR 160 |
| | OCCUPANTS. PLEASE PROVIDE THE LIFE SAFETY PLANS TO THE |
| | PUBLIC WAY. |
| | |
| | 6) ANOTHER ISSUE THAT IS BORDER LINE IS THE OCCUPANT |
| | LOAD ON THE SECOND FLOOR AND A THIRD REQUIRED STAIRWAY |
| | 2010 FBC-B TABLE 1021.1 IF 501 OCCUPANTS ARE LOCATED ON |
| | THE 2ND FLOOR THEN A THIRD REQUIRED EXIT STAIR WILL |
| | ALSO BE REQUIRED. |
| | |
| | 7) ) THE PLANS DO NOT PROVIDE A SECTION THROUGH THE |
| | MONUMENTAL STAIRWAY, PLEASE PROVIDE SUCH SECTION |
| | PROVIDING DETAILS SUCH AS DRAFT CURTAIN AND SPRINKLER |
| | LOCATION. |
| | 2010 FBC-B 708.2 EXCEPTION 2.1. WHERE THE AREA OF THE |
| | FLOOR OPENING BETWEEN STORIES DOES NOT EXCEED TWICE THE |
| | HORIZONTAL PROJECTED AREA OF THE ESCALATOR OR STAIRWAY |
| | AND THE OPENING IS PROTECTED BY A DRAFT CURTAIN AND |
| | CLOSELY SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13. |
| | IN OTHER THAN GROUPS B AND M, THIS APPLICATION IS |
| | LIMITED TO OPENINGS THAT DO NOT CONNECT MORE THAN FOUR |
| | STORIES. PLEASE NOTE THIS EXCEPTION IS ONLY FOR |
| | BUSINESS & MERCANTILE, NOT FOR AN ASSEMBLY USE, PLEASE |
| | PROVIDE HOW THIS CODE VIOLATION WILL BE COMPLIED. |
| | |
| | 8) SHEET # A-3.0 INDICATES A NEW ROOF CURB PLEASE |
| | PROVIDE TTHE MANUFACTURES CUT SHEETS ON THE NEW ROOF |
| | CURB FOR THIS WIND SPEED, 170 MPH V-ULT. |
| | |
| | 9A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 9B) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 9C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 9D) A PLAN REVIEW STOP WILL BE PUT ON THIS PROJECT |
| | UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY THE |
| | CHIEF BUILDING INSPECTOR KEN CONRAD: |
| | |
| | PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected] |
| | |
| | 2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |