| Date |
Text |
| 2013-03-20 15:38:03 | 770 NORTHPOINT PARKWAY - SUITE #200 |
| | PERMIT #13030378 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR |
| | AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL |
| | HAVE "NO SMOKING" SIGNS POSTED.WHERE SMOKING IS |
| | PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL |
| | BE PROVIDED. |
| | |
| | SHEET A-1.-0: CORRIDOR #208 HAS A DOOR THAT WILL SWING |
| | AGAINST THE DIRECTION OF EGRESS NO MATTER WHICH WAY THE |
| | SWING IS ORIENTED. ALSO THIS DOOR IS EQUIPPED WITH A |
| | KEYPAD THAT WILL PREVENT OCCUPANTS FROM FREELY |
| | ACCESSING EXIT STAIR #210. DOORS SHALL BE ARRANGED TO |
| | BE OPENED READILY FROM THE EGRESS SIDE WHENEVER THE |
| | BUILDING IS OCCUPIED. LOCKS, IF PROVIDED, SHALL NOT |
| | REQUIRE THE USE OF A KEY, TOOL, OR SPECIAL KNOWLEDGE OR |
| | EFFORT FOR OPERATION FROM THE EGRESS SIDE. |
| | |
| | SHEET E4.1: NOTE #8 INDICATES A KEYPAD TO BE INSTALLED |
| | AT THE FLOOR EXTERIOR DOOR. HOW WILL THE ELECTRICAL BE |
| | ROUTED TO THIS DEVICE? NOTE: THE STAIRWELL CANNOT BE |
| | USED. |
| | |
| | NO FIRE ALARM DESIGN SHOW. PER FBC SECTION907.1.1, |
| | "CONSTRUCTION DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE, THE |
| | FLORIDA FIRE PREVENTION CODE, AND RELEVANT LAWS, |
| | ORDINANCES, RULES AND REGULATIONS, AS DETERMINED BY THE |
| | BUILDING OFFICIAL." |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |