| Plan Review Notes For Permit 13030378 |
| Permit Number |
13030378 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-15 12:41:30 | 13030378 | | | 770 NORTH POINT PKWY #200 | | | MEDICAL OFFICE INTERIOR | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENT. | | | | | | WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES | | | A SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT | | | GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT | | | GROUND. NEC 517.13 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|