| Plan Review Notes For Permit 13030376 |
| Permit Number |
13030376 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-05-21 16:00:25 | MECHANICAL PROVISO: | | | 2010 FBC-ENERGY CONSERVATION 503.2.5.4 SHUTOFF DAMPER | | | CONTROLS. | | | BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE | | | EQUIPPED WITH DAMPERS | | | THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES | | | SERVED ARE NOT IN USE. | | | VENTILATION OUTSIDE AIR DAMPERS SHALL BE CAPABLE OF | | | AUTOMATICALLY SHUTTING OFF | | | DURING PREOCCUPANCY BUILDING WARMUP, COOLDOWN, AND | | | SETBACK, EXCEPT WHEN | | | VENTILATION REDUCES ENERGY COSTS (E.G., NIGHT PURGE) OR | | | WHEN VENTILATION MUST | | | BE SUPPLIED TO MEET CODE REQUIREMENTS. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|