2013-03-14 15:43:27****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A PLAN WHICH SHOWS LOCATION OF PROPOSED
 IMPROVEMENTS. THE APPLICATION IS FOR ONE DOOR AND
 REPLACING CEILING, BUT A RANGE OF ADDRESSES WAS GIVEN
 ON THE APPLICATION.
  
 2. PLAN IS TO SHOW OCCUPANCY CLASSIFICATION OF THE
 SPACE(S) AFFECTED, FBC CHAPTER 3 AND OCCUPANT LOAD. IF
 THE DOOR IS TO BE INSTALLED AT THE RESTAURANT, PROVIDE
 HARDWARE INFORMATION AND EXITING INFORMATION. PANIC
 EXIT HARDWARE MAY BE REQUIRED, OR HARDWARE IN
 ACCORDANCE WITH THE EXCEPTION FOR THE FRONT DOOR, FBC
 1008.1.10.
  
 3. INDICATE THE DOOR PROPOSED. IF PANIC EXIT HARDWARE
 IS REQUIRED, THE HARDWARE OPTION IS TO BE INCLUDED IN
 THE PRODUCT APPROVAL.
  