| Plan Review Notes For Permit 13030332 |
| Permit Number |
13030332 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-04-03 17:16:33 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | FROM PREVIOUS LIST: | | | | | | 1. REVISE PLAN TO INCLUDE ALL STRUCTURAL DETAILS | | | REQUIRED FOR INSPECTIONS AND TO SHOW RESISTANCE TO WIND | | | LOADS FBC R 301. FOR INSTANCE: ENGINEER'S SPECIFICATION | | | FOR FOOTING (CONTRACTOR'S PLAN PROPOSES FOOTER, | | | ENGINEER'S DETAIL SHOWS "EXISTING SLAB" BUT NO MINIMUM | | | DIMENSIONS OTHER THAN EDGE DISTANCE), GIRT TO POST, | | | DOOR JAMB TO SLAB, 1X2 TO HOST, CABLE TO CORNER. | | | | | | 2. PLAN IS NOT ENTIERELY LEGIBLE. PLEASE PROVIDE | | | LEGIBLE PLANS, FBC 107. | | | | | | 2ND REVIEW, THE SITE SPECIFIC WAS REVISED BUT NOT THE | | | SCREEN ENCLOSURE DETAIL PLAN. | | | | | | CONTRACTOR CALLED, LEFT MESSAGE - EITHER REVISE PLAN TO | | | INCLUDE ALL PERTINENT STRUCTURAL DETAILS OR CALL ME TO | | | DISCUSS. | | | | | | |
|