| Plan Review Notes For Permit 13030266 |
| Permit Number |
13030266 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-19 09:04:24 | PROVISO - FBC M 507.2.1.1 TYPE I HOOD SYSTEMS SHALL BE | | | DESIGNED AND INSTALLED TO AUTOMATICALLY ACTIVATE THE | | | EXHAUST FAN WHENEVER COOKING OPERATIONS OCCUR. THE | | | ACTIVATION OF THE EXHAUST FAN SHALL OCCUR THROUGH AN | | | INTERLOCK WITH THE COOKING APPLIANCES, BY MEANS OF HEAT | | | SENSORS OR BY MEANS OF OTHER APPROVED METHODS | | | |
|