| 2013-03-11 09:49:15 | BUILDING REVISION CHECKLIST. |
| | |
| | 1- REVISION FORM STATES "CHANGE WINDOWS TO SINGLE |
| | HUNG". THERE ARE TWO DIFFERENT AND INCOMPLETE PRODUCT |
| | APPROVALS STAPLED TOGETHER. FRONT PAGE NOA 12-0516.02 |
| | IS FOR FRENCH DOORS AND IS MISSING THE REST OF THE NOA |
| | PACKAGE. THEN, THERE ARE THREE PAGES SUBMITTED FOR NOA |
| | 11-1013.19 WHICH ARE FOR THE SINGLE HUNG WINDOWS. AND, |
| | IS ALSO MISSING THE REST OF THE NOA PACKAGE. |
| | CLARIFY THE FOLLOWING: |
| | A) ARE ALL THE FRENCH DOORS GOING TO BE REPLACED ALSO. |
| | IF, SO, THEN PROVIDE 2 COMPLETE COPIES OF PRODUCT |
| | APPROVALS AS REQUIRED BY DCA RULE 9N-3. AND UPDATE |
| | VALUE ACCORDINGLY. |
| | ***NOTE: FRONT PAGE OF COPY SUBMITTED IS NOT LEGIBLE. |
| | COPY WAS TAKEN WITH THE ARCHITECT'S REVIEW STAMP |
| | COVERING THE PRODUCT APPROVAL INFORMATION. |
| | |
| | B) PROVIDE 2 COMPLETE COPIES OF PRODUCT APPROVAL FOR |
| | SINGLE HUNG WINDOWS. |
| | |
| | C) CLARIFY IF THE EXTERIOR WINDOWS ARE GOING TO BE |
| | REPLACED OR IF THIS PRODUCT APPROVAL IS ONLY FOR THE |
| | TWO NEW WINDOWS IN THE MASTER BATHROOM. AND UPDATE |
| | VALUE ACCORDINGLY. |
| | |
| | D) THIS HOUSE IS LOCATED IN FLOOD ZONE A5. REPLACING |
| | DOORS AND WINDOWS ARE CONSIDERED SUBSTANTIAL |
| | IMPROVEMENTS AND MAY REQUIRE THE FINISH FLOOR OF THE |
| | HOUSE TO BE ELEVATED TO 7'-6" AS REQUIRED BY SEC. |
| | 94-541 OF CITY CODE. |
| | |
| | 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS |
| | TO FBC. |
| | ***NOTE: ARCHITECT APPROVED THE FRONT PAGE OF THE |
| | FRENCH DOORS NOA ONLY. |
| | |