| Plan Review Notes For Permit 13030161 |
| Permit Number |
13030161 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2013-06-27 14:38:13 | SEE PROVISIO ON PLANS FROM JW. RL | | 2013-06-17 16:23:25 | MECHANICAL PROVISO: | | | PROVIDE A DETAIL ON THE CURB TO ROOF TIE DOWN | | | AND RTU TO CURB TIE DOWN BY THE ENGINEER OF RECORD | | | BY 1ST INSPECTION. PER SECTION 2010 FBC-M 301.12 WIND | | | RESISTANCE. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|