| Plan Review Notes For Permit 13030161 |
| Permit Number |
13030161 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-11 14:27:59 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | FBC PLUMBING 403.2 SEPARATE FACILITIES ARE REQUIRED FOR | | | EACH SEX, WITH THE EXCEPTION (3) SEPARATE FACILITIES | | | SHALL NOT BE REQUIRED IN BUSINESS AND MERCANTILE | | | OCCUPANCIES WITH A TOTAL FLOOR AREA OF 3,000 SQUARE | | | FEET (279 M2) OR LESS. | | | SHEET SP 1 LISTS THE OCCUPANCY AS BUSINESS WITH 7,924 | | | S.F. PLEASE PROVIDE THE OCCUPANCY TYPE/S AND OCCUPANT | | | LOAD FOR EACH TYPE. | | | | | | COMMERCIAL OCCUPANCIES SUCH AS BUSINESS, MERCANTILE, | | | STORAGE, ETC. REQUIRE A HI/LO DRINKING FOUNTAIN UNLESS | | | THERE ARE 15 OR LESS OCCUPANTS. | | | FBC PLUMBING TABLE 403.1(E, F) | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|