2013-03-21 11:48:12BUILDING PLAN REVIEW
 PERMIT: 13030161
 ADD: 5908 GEODGIA AVE
 CONT: IDEAL FLOORING & REMODELING
 TEL: (561)523-9643
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 3/21/2013
 ACTION: DENIED
  
 1) THE COVER SHEET UNDER THE HEADING OF SITE DATA NOR
 BUILDING INFORMATION DOES NOT PROVIDE THE MINIMUM
 BUILDING TYPE 2010 FBC-B TABLE 503.
  
 2) THE COVER SHEET INDICATES THE SQUARE FOOTAGE OF THE
 BUILDING AS 4491 SQ FT AND A EXISTING MEZZANINE AS 3078
 SQ FT. IF THIS SQUARE FOOTAGE IS CORRECT THEN THE SO
 CALLED MEZZANINE IS A TRUE SECOND FLOOR, SEE 2010 FBC-B
 505.2 AND EXCEPTIONS. PLEASE SHOW MEZZANINE LEVEL AND
 EXITING.
  
 3) IF THE COVER SHEET IS CORRECT WITH THE SQUARE
 FOOTAGE FOR THE SECOND FLOOR THEN PLEASE SHOW THE
 SECOND FLOOR LEVEL AND EXITING OF THE 2ND FLOOR.
 MINIMUM PLAN REVIEW CRITERIA FOR REQUIREMENTS FOR
 COMMERCIAL PLAN REVIEW. 107.3.5
 FLOOR PLANS- SECOND FLOOR
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
  
 LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
  
 4) ON SHEET D1 & A1 ON THE EAST WALL THE PLANS INDICATE
 CUTTING IN A NEW DOORWAY THE SITE PLAN (COVER SHEET)
 WHEN SCALED INDICATES 3'-0" TO THE PROPERTY LINE,
 PLEASE PROVIDE COMPLIANCE WITH SECTIONS 2010 FBC-B
 TABLE 602 & TABLE 705.8 FOR EXISTING OPENINGS AND THE
 NEW PROPOSED OPENING.
  
 5) SHEET A1 DOES NOT INDICATE ANY OCCUPANCY SEPERATION
 WALL BETWEEN THE WAREHOUSE AND THE NEW MERCANTILE
 OCCUPANCY, PLANS DO NOT INDICATE IF THE WAREHOUSE IS A
 S1 OR S2 OCCUPANCY PLEASE REVIEW 2010 FBC-B TABLE
 508.4.
  
 6) SHEET A1 DOOR # 107 DOES NOT INDICATE BEING FIRE
 RATED, AGAIN IT WILL DEPEND ON THE STORAGE OCCUPANCY
 FOR THE FIRE RATING TABLE 508.4 AND TABLE 715.4.
  
 7) THE PLANS INDICATE NEW EXTERIOR OPENINGS PLEASE
 REVIEW THE FOLLOWING;
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  