Plan Review Notes
Plan Review Notes For Permit 13030136
Permit Number 13030136
Review Stop M
Sequence Number 1
Notes
Date Text
2013-03-22 10:47:21PLANS DENIED
 1) HOODS AND COOLERS REQUIRE SEPARATE
 APPLICATION, PLANS AND PERMIT.
 2) PROVIDE OUTSIDE AIR CALCULATIONS
 ON THE PLANS. PER SECTION 403.3 OUTDOOR
 AIRFLOW RATE AND TABLE 403.3 FBC (M) 2010
 3) REFER TO SECTION 601.4 BALANCED RETURN AIR
 2010 FBC (M). FOR THE OFFICE.
 4) REFER TO SECTION 304.11 GUARDS 2010 FBC (M)
 5) REFER TO SECTION 503.2 .4.4 SHUT OFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE.FOR FRESH AIR
 6) PROVIDE MANUFACTURERS INFORMATION ON THE APPLIANCES
 TO SEE IF HOOD IS REQUIRED WITH THE PLANS.
 PLAN REVIEW BY HAROLD MOSER
 561- 805 6732
 [email protected]