| Notes |
| Date |
Text |
| 2013-03-22 10:47:21 | PLANS DENIED | | | 1) HOODS AND COOLERS REQUIRE SEPARATE | | | APPLICATION, PLANS AND PERMIT. | | | 2) PROVIDE OUTSIDE AIR CALCULATIONS | | | ON THE PLANS. PER SECTION 403.3 OUTDOOR | | | AIRFLOW RATE AND TABLE 403.3 FBC (M) 2010 | | | 3) REFER TO SECTION 601.4 BALANCED RETURN AIR | | | 2010 FBC (M). FOR THE OFFICE. | | | 4) REFER TO SECTION 304.11 GUARDS 2010 FBC (M) | | | 5) REFER TO SECTION 503.2 .4.4 SHUT OFF DAMPER CONTROLS | | | 2010 FLORIDA ENERGY CODE.FOR FRESH AIR | | | 6) PROVIDE MANUFACTURERS INFORMATION ON THE APPLIANCES | | | TO SEE IF HOOD IS REQUIRED WITH THE PLANS. | | | PLAN REVIEW BY HAROLD MOSER | | | 561- 805 6732 | | | [email protected] |
|