Plan Review Notes
Plan Review Notes For Permit 13030136
Permit Number 13030136
Review Stop E
Sequence Number 1
Notes
Date Text
2013-03-19 13:45:5513030136
 712 S. DIXIE HIGHWAY
 DUNKIN DONUTS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
  
 PROVIDE A SAFETY LABELING SCHEDULE ON THE PLAN FOR
 FLASH PROTECTION, PANEL BOARDS AND THE MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION T505.3
  
 VERIFY COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS FOR CONTROL OF INTERIOR AND EXTERIOR
 LIGHTING INCLUDING SIGNS. FBC ENERGY CONSERVATION 505
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
  
 NOTE:
 SEPARATE PERMITS ARE REQUIRED FOR VOICE, DATA, SIGNS,
 LOW VOLTAGE, SITE LIGHTING, ETC.
  
  