| 2013-03-19 13:45:55 | 13030136 | | | 712 S. DIXIE HIGHWAY | | | DUNKIN DONUTS | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE ON THE PLAN FOR | | | FLASH PROTECTION, PANEL BOARDS AND THE MAIN | | | DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 | | | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC ENERGY CONSERVATION T505.3 | | | | | | VERIFY COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS FOR CONTROL OF INTERIOR AND EXTERIOR | | | LIGHTING INCLUDING SIGNS. FBC ENERGY CONSERVATION 505 | | | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. NEC 250.94 | | | | | | | | | NOTE: | | | SEPARATE PERMITS ARE REQUIRED FOR VOICE, DATA, SIGNS, | | | LOW VOLTAGE, SITE LIGHTING, ETC. | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|