| 2013-03-20 15:21:36 | BUILDING PLAN REVIEW |
| | PERMIT: 13030136 |
| | ADD: 7512 S DIXIE HWY |
| | CONT: VENTURA ARCHITECTURE DEVELOPMENT |
| | TEL: (954)423-1362 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 3/20/2013 |
| | ACTION: DENIED |
| | |
| | 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING, FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS TRUELITE STOREFRONT NOA 11-1207.07 |
| | NON-IMPACT GLASS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, HARDI-PLANK |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 3) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| | 1609.1.4. |
| | FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 & |
| | EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE |
| | INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING |
| | SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT |
| | SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS, |
| | WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE |
| | PLAN REVIEW AND PERMIT ISSUANCE. |
| | |
| | 4) SHEEET A-8 A NOTE INDICATES THE USE OF |
| | PAPERBACKGALVANIZED WIRE LATH OVER 5/8 INCH CDX |
| | PLYWOOD, PLEASE REVIEW SECTION 2010 FBC-B 1404.2.1 |
| | REQUIED BOND BREAK. |
| | |
| | 5) SHEET S-1 NOTE INDICATES THE PLANS WERE DESIGNED TO |
| | THE 2010 RESIDENTIAL BUILDING CODEHVHZ SECTIONS, THIS |
| | IS A COMMERCIAL BUILDING TO BE DESIGNED TO THE 2010 |
| | FBC-BUILDING CODE, AND TTHE WIND DESIGN IS NOT IN THE |
| | HIGH VELOCITY HURRICANE ZONE BUT IN A 170 MPH 3 SECOND |
| | GUST HIGH WIND DEBRIS REGION. |
| | |
| | 6) S-3 THE WIND DESIGN PRESSURES PROVIDED DO NOT |
| | INDICATE AS TO HOW MANY SQ FT ARE USED FOR EACH |
| | ASSEMBLY TYPE FOR COMPONENTS & CLADDING, IS IT 10 SQ |
| | FT, 20 SQ FT , 50 SQ FT OR 100 SQ FT ? 1609.4.4.1. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |