| 2013-03-11 10:59:41 | 5720 PREMIER PARK DRIVE |
| | PERMIT #13030119 |
| | MASTER #12120739 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NO PREACTION SYSTEM EQUIPMENT INFORMATION SUBMITTED AND |
| | NEITHER THE SPRINKLER SHOP DRAWINGS NOR FIRE ALARM SHOP |
| | DRAWINGS (PERMIT #13030226) SHOW THE DETECTION DEVICES |
| | TO BE USED WITH THE DOUBLE-INTERLOCK PREACTION SYSTEM |
| | PROTECTING THE VAULT AND SERVER ROOM. |
| | |
| | ESFR SPRINKLERS HAVE BEEN DELETED ABOVE THE NORTH |
| | PORTION OF OPEN AREA #112. THERE ALSO 5 BRANCHLINES |
| | THAT ARE NOT CONNECTED TO THE GRID SYSTEM AT EITHER THE |
| | NORTH OR SOUTH END. |
| | |
| | DESIGN AREA #4 INDICATES A REDUCED HYDRAULIC AREA FOR |
| | UTILIZING QUICK-RESPONSE SPRINKLERS; HOWEVER, THE 155F |
| | (TEMPERATURE) TYCO EC-8 RECESSED PENDENT SPRINKLER IS |
| | STANDARD RESPONSE ACCORDING TO TABLE B IN THE CUT |
| | SHEETS. |
| | |
| | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND |
| | END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE |
| | PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE |
| | LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE |
| | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING |
| | UPWARD MOVEMENT. |
| | |
| | PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE MAXIMUM |
| | NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND RADIUS |
| | PERMITTED IN THE LISTING DATA. |
| | |
| | SUBMIT PRODUCT DATA FOR THE FLEXIBLE SPRINKLER DROPS |
| | PROPOSED TO BE INSTALLED. INDICATE IF THE DROPS ARE |
| | BRAIDED OR UNBRAIDED. |
| | |
| | INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE |
| | USED. |
| | |