2013-03-07 12:25:342275 PALM BEACH LAKES BOULEVARD
 PERMIT #13030118
 MASTER #12030334
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PER NFPA 24 (2010 ED) SECTION 7.2.3 FIRE HYDRANTS SHALL
 BE LOCATED NOT LESS THAN 40 FEET FROM THE BUILDING
 BEING PROTECTED.
  
 PER NFPA 24 (2010 ED) SECTION 5.2.1 PIPE SMALLER THAN
 6-INCHES IN DIAMETER SHALL NOT BE INSTALLED AS A
 PRIVATE SERVICE MAIN SUPPLYING FIRE HYDRANTS.
  
 NOTE: FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES
 OF 7?-6? TO THE FRONT AND SIDES AND 4? TO THE BACKSIDE
 PER SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION. PARKING
 STALLS LOCATED WITHIN THIS CLEARANCE ZONE SHALL BE
 INDICATED WITH "NO PARKING BY ORDER OF THE FIRE
 MARSHAL" (OR SIMILAR).
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE