| 2013-03-07 12:25:34 | 2275 PALM BEACH LAKES BOULEVARD | | | PERMIT #13030118 | | | MASTER #12030334 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION. | | | | | | PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR | | | SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN | | | POSITION. | | | | | | PER NFPA 24 (2010 ED) SECTION 7.2.3 FIRE HYDRANTS SHALL | | | BE LOCATED NOT LESS THAN 40 FEET FROM THE BUILDING | | | BEING PROTECTED. | | | | | | PER NFPA 24 (2010 ED) SECTION 5.2.1 PIPE SMALLER THAN | | | 6-INCHES IN DIAMETER SHALL NOT BE INSTALLED AS A | | | PRIVATE SERVICE MAIN SUPPLYING FIRE HYDRANTS. | | | | | | NOTE: FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES | | | OF 7?-6? TO THE FRONT AND SIDES AND 4? TO THE BACKSIDE | | | PER SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION. PARKING | | | STALLS LOCATED WITHIN THIS CLEARANCE ZONE SHALL BE | | | INDICATED WITH "NO PARKING BY ORDER OF THE FIRE | | | MARSHAL" (OR SIMILAR). | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|