2013-03-19 14:17:46600 SOUTH ROSEMARY AVENUE - #170
 PERMIT #13030091
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 SHEET A-0: PLAN INDICATES A MERCATILE OCCUPANCY WHICH
 SHOULD BE CORRECTED TO AN ASSEMBLY OCCUPANCY.
  
 SHEET A-2: CONFIRM EXISTING EXIT DOORS ARE EQUIPPED
 WITH PANIC HARDWARE. NOTE: FOR OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE
 SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE
 LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED
 LOCK.
  
 SHEET A-2: PRIVATE DINING "A" & "B" (DOOR #13 AND #14)
 HAS DOORS THAT ARE PART OF THE EXIT ACCESS AND ARE
 REQUIRED TO BE SIDE-SWINGING IN LIEU OF SLIDING POCKET
 DOORS.
  
 SHEET E-3: NO EXIT SIGNS SHOWN IN PRIVATE DINING "A" OR
 "B"; REFER TO LIFE SAFETY PLAN FOR EXIT SIGN LOCATIONS.
  
 SHEET K1.1: BURNER RANGE #105 DOES NOT APPEAR TO BE
 LOCATED UNDER THE KITCHEN EXHAUST HOOD OR PROTECTED BY
 THE WET-CHEMICAL EXTINGUISHING SYSTEM.
  
 CONFIRM PIZZA OVEN IS GAS FUELED ONLY (NO SOLID FUEL;
 IE WOOD).
  
 SEPARATE PLANS AND PERMIT NEEDED TO ENSURE EXISTING
 KITCHEN HOOD SUPPRESSION SYSTEM IS PROPERLY PROTECTING
 NEW COOKING EQUIPMENT.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  