| 2013-03-19 14:17:46 | 600 SOUTH ROSEMARY AVENUE - #170 |
| | PERMIT #13030091 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR |
| | AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL |
| | HAVE "NO SMOKING" SIGNS POSTED.WHERE SMOKING IS |
| | PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL |
| | BE PROVIDED. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | SHEET A-0: PLAN INDICATES A MERCATILE OCCUPANCY WHICH |
| | SHOULD BE CORRECTED TO AN ASSEMBLY OCCUPANCY. |
| | |
| | SHEET A-2: CONFIRM EXISTING EXIT DOORS ARE EQUIPPED |
| | WITH PANIC HARDWARE. NOTE: FOR OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 100 OR MORE PERSONS, PANIC HARDWARE |
| | SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. |
| | NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT |
| | BE RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| | PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| | AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| | READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| | UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| | SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE |
| | LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED |
| | LOCK. |
| | |
| | SHEET A-2: PRIVATE DINING "A" & "B" (DOOR #13 AND #14) |
| | HAS DOORS THAT ARE PART OF THE EXIT ACCESS AND ARE |
| | REQUIRED TO BE SIDE-SWINGING IN LIEU OF SLIDING POCKET |
| | DOORS. |
| | |
| | SHEET E-3: NO EXIT SIGNS SHOWN IN PRIVATE DINING "A" OR |
| | "B"; REFER TO LIFE SAFETY PLAN FOR EXIT SIGN LOCATIONS. |
| | |
| | SHEET K1.1: BURNER RANGE #105 DOES NOT APPEAR TO BE |
| | LOCATED UNDER THE KITCHEN EXHAUST HOOD OR PROTECTED BY |
| | THE WET-CHEMICAL EXTINGUISHING SYSTEM. |
| | |
| | CONFIRM PIZZA OVEN IS GAS FUELED ONLY (NO SOLID FUEL; |
| | IE WOOD). |
| | |
| | SEPARATE PLANS AND PERMIT NEEDED TO ENSURE EXISTING |
| | KITCHEN HOOD SUPPRESSION SYSTEM IS PROPERLY PROTECTING |
| | NEW COOKING EQUIPMENT. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE |
| | ALARM SYSTEM. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |