Plan Review Notes
Plan Review Notes For Permit 13030087
Permit Number 13030087
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-03-12 14:59:20FIRE PLAN REVIEW
 PERMIT # 13030087
 ADDRESS: 1901 PALM BEACH LAKES BOULEVARD
 CONTRACTOR: AB FIRE EQUIPMENT
 PHONE: 954-570-9860
 ACTION: PASSED
  
 FLORIDA FIRE PREVENTION CODE 2010 EDITION
  
  
 1. A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG
 THE EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A
 MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE
 DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR
 AND SHALL CLEARLY IDENTIFY THE HAZARD PROTECTED PER FBC
 904.11.1.
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 804-4709
 [email protected]
  