| Plan Review Notes For Permit 13030078 |
| Permit Number |
13030078 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-10 17:19:10 | 2010 FBC | | | | | | REVISION IS DENIED BY BUILDING | | | | | | 1) THE STRUCTURAL DESIGNER OF RECORD FOR THIS PROJECT | | | IS JOHN AVERKAMP, P.E.39337. ANY STRUCTURAL CHANGES TO | | | THE DESIGN ARE REQUIRED TO BE MADE BY THE ENGINEER OF | | | RECORD AND SIGNED AND SEALED BY HIM PER FS 471 AND FAC | | | 61G15-23.002. THE REVISION THAT WAS SUBMITTED TO CHANGE | | | FROM ROOF TRUSSES TO A CONVENTIONAL FRAMED ROOF SYSTEM | | | WAS PREPARED, SIGNED AND SEALED BY THE ARCHITECT. THE | | | ARCHITECT WILL HAVE TO ASSUME THE STRUCTURAL | | | RESPONSIBILITY FOR THE PROJECT AND SUBMIT NEW | | | STRUCTURAL DRAWINGS IN ORDER TO REVISE THE STRUCTURAL | | | PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|