| 2013-03-05 10:06:52 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | 1. PLANS NOT AVAILABLE FOR 03030279, 03090045. PLANS |
| | AVAILABLE FOR 03052171. IT APPEARS THAT THE SCOPE FOR |
| | 03030279 IS THE SAME AS 03052171. |
| | |
| | IF CONTRACTOR WOULD LIKE FOR A PERMIT TO BE ISSUED FOR |
| | THE SCOPE OF WORK FOR 03052171 AND 03030279, AND A |
| | SEPARATE APPLICATION AND PERMIT DOCUMENTS ADDRESSING |
| | THE FOLLOWING COMMENTS, PLEASE ADVISE. |
| | |
| | 2. FOR THE WINDOWS, PERMIT 03030045, PLEASE ADDRESS THE |
| | FOLLOWING COMMENTS: |
| | |
| | PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, SIZES, |
| | WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING |
| | CANNOT BE REDUCED BY MORE THAN 5%. |
| | |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | FAC9N-3. |
| | |
| | IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| | 301.2.1.2. IF WINDOWS ARE LARGE MISSILE IMPACT RATED, |
| | DISREGARD THIS COMMENT. |
| | |
| | IF THE WINDOWS ARE NOT IMPACT RATED, IMPACT PROTECTION |
| | REQUIRED. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS |
| | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE |
| | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM |
| | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF). |
| | |
| | |
| | |