| 2013-04-17 17:12:24 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | COMMENTS FROM PREVIOUS LISTS: |
| | |
| | 1. FOR THE WINDOWS : REVISE THE PLAN TO SHOW ROOM |
| | DESIGNATIONS. NOTE EXISTING CONDITIONS (TYPE OF WINDOW) |
| | AND OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. |
| | THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. |
| | |
| | FIRST PLAN SHOWED 60" WINDOW AT BEDROOM, SECOND SHOWS A |
| | 48". IF THIS WINDOW IS 48" HIGH, REVISE PLAN TO INCLUDE |
| | TYPE OF WINDOW THAT IS EXISTING. |
| | |
| | 3RD REVIEW, A PLAN SUBMITTED WITH NO WINDOWS SHOWN, AND |
| | DOES NOT CORRELATE WITH ELEVATIONS AS THERE IS NO |
| | COMPASS NORTH ON THE PLAN. TYPE OF EXISTING WINDOWS NOT |
| | PROVIDED. |
| | |
| | 2. FOR THE SHUTTERS: |
| | |
| | THE INSTALLATION SCHEDULE SUBMITTED DOES NOT INCLUDE |
| | THE INFORMATION "SHUTTER MOUNTING CONNECTIN TYPE", SEE |
| | SHEETS 12 THROUGH 15 OF THE NOA. FOR INSTANCE, |
| | "ALTERNATIVE 1" WOULD REQUIRED 6" OC ANCHOR SPACING, |
| | SEE DETAIL. MOST OF THE CONNECTION TYPES APPEAR TO |
| | REQUIRE 6" SPACING, BUT 8" IS PROPOSED. HOWEVER WITHOUT |
| | KNOWING WHICH INSTALLATION METHOD (CONNECTION TYPE) IS |
| | PROPOSED, COMPLIANCE CANNOT BE DETERMINED. |
| | |
| | PRESSURES ARE TOO HIGH FOR THE SHUTTERS WHICH ARE |
| | LIMITED TO -72PSF. IT IS NOT CLEAR WHY YOU HAVE |
| | SPECIFIED THESE PRESSURES: +-45 WOULD MEET MINIMUM CODE |
| | COMPLIANCE FOR ALL OPENINGS. FBC R 301 |
| | |