| 2013-06-29 07:52:00 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1-2. OK |
| | |
| | 3. BEDROOM #1 DOES NOT EMERGENCY MEANS OF ESCAPE AND |
| | RESCUE WHICH COMPLIES WITH FBC R 310. IT APPEARS THAT |
| | THIS WAS CONVERTED FROM A PORCH TO A BEDROOM WITHOUT A |
| | PERMIT. PROVIDE AN EGRESS OPENING. |
| | |
| | 2ND REVIEW - WINDOW SIZE INCREASED BUT NO DETAIL |
| | PROVIDED FOR NEW ENLARGED OPENING, FBC 109, FBC 2010 |
| | RESIDENTIAL 301. |
| | |
| | 4. OK |
| | |
| | 5. PROVIDE A STRUCTURAL DETAIL FOR THE INFILL FBC R |
| | 301, FBC 107. |
| | |
| | NOT ADDRESSED. |
| | |
| | 6. OK |
| | |
| | 7. AS IT APPEARS THAT UNINHABITABLE SPACE WAS CONVERTED |
| | TO HABITABLE SPACE, IMPACT FEE ASSESSMENT REQUIRED. |
| | CONTACT 561-233-5025 FOR MORE INFORMATION. REVISE PLAN |
| | TO REFLECT CONVERSION OF PORCH TO LIVING SPACE WITH |
| | APPLICABLE DETAILS. |
| | |
| | NEW COMMENTS: |
| | |
| | 8. SHUTTER PRODUCT APPROVALS SUBMITTED ON 2ND REVIEW. |
| | COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE |
| | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER |
| | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. |
| | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET |
| | AT |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | 9. CONTRACTOR INFORMED THAT NO MECHANICAL WORK IS |
| | PROPOSED, ALL EXISTING. THERE IS NO RECORD OF AIR |
| | CONDITIONING INSTALLED AT THIS LOCATION. PLEASE |
| | ADDRESS. FBC 107 |
| | |
| | |
| | |