| Plan Review Notes For Permit 13030009 |
| Permit Number |
13030009 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-29 13:52:48 | | | | FBC 2010 FUEL GAS REVIEW #1 | | | DENIED: | | | | | | GAS PERMIT , PLAN, APPLICATION, AND FEE REQUIRED. | | | NOT ENOUGH INFORMATION TO DO A GAS REVIEW. PLEASE | | | SUBMIT THE FOLLOWING: | | | | | | GAS PERMIT APPLICATION REQUIREMENTS | | | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL | | | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING | | | IN THE CITY OF WEST PALM BEACH: | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2010 FUEL GAS. | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2010 | | | FUEL GAS APPENDIX A ? USE OF CAPACITY SECTION A.3.1(4) | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|