| 2013-03-01 17:00:09 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION |
| | IS TOO LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. PERMIT |
| | APPLICATION STATES 2000 S.F. OR ROOF AREA. THIS HOUSE |
| | ROOFING SQUARE FOOTAGE IS A LOT MORE THAN 2,000 S.F. |
| | REVISE THE TOTAL ROOF SQUARE FEET AND VALUATION. |
| | |
| | 2- SEC. 105.15 OF CITY AMENDMENTS TO FBC. FLORIDA |
| | STATUTE SEC. 553.844. (3)(C) REQUIRES THAT ANY PERMIT |
| | WHICH THE COST IS MORE THAN $50,000 NEED TO PROVIDE |
| | PROVISION OF OPENINGS PROTECTION. ALL THE GLAZING ON |
| | DOORS AND WINDOWS NEED TO HAVE HURRICANE IMPACT |
| | PROTECTION. PROVIDE INFORMATION SOWING EXISTING |
| | OPENINGS IMPACT PROTECTION. SEE BELOW FOR COPY OF |
| | FLORIDA STATUTE SECTION: |
| | |
| | (C) ANY ACTIVITY REQUIRING A BUILDING PERMIT THAT IS |
| | APPLIED FOR ON OR AFTER JULY 1, 2008, AND FOR WHICH THE |
| | ESTIMATED COST IS $50,000 OR MORE, MUST INCLUDE |
| | PROVISION OF OPENING PROTECTIONS AS REQUIRED WITHIN THE |
| | FLORIDA BUILDING CODE FOR NEW CONSTRUCTION FOR A |
| | BUILDING THAT IS LOCATED IN THE WIND-BORNE DEBRIS |
| | REGION AS DEFINED IN S. 1609.2 OF THE INTERNATIONAL |
| | BUILDING CODE (2006) AND THAT HAS AN INSURED VALUE OF |
| | $750,000 OR MORE, OR, IF THE BUILDING IS UNINSURED OR |
| | FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT |
| | PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR |
| | PURPOSES OF AD VALOREM TAXATION OF $750,000 OR MORE. |
| | |
| | 3- WHEN THE VALUE OF THE STRUCTURE IS MORE THAN |
| | $300,000, THEN ROOF TO WALL CONNECTIONS ARE REQUIRED BY |
| | SEC. 611.8 OF 2010 FBC-EXISTING BUILDING. |
| | |
| | 4- SPECIFY ON CONCRETE TILE PRODUCT APPROVAL SUBMITTED |
| | WHICH SPECIFIC CONCRETE TILE AND APPLICATION |
| | (INTER-DEPENDENT OR INDEPENDENT) IS GOING TO BE |
| | INSTALLED. AND, PROVIDE THE MOMENT OF RESISTANCE |
| | CALCULATIONS (RAS 127) TO VERIFY COMPLIANCE WITH THE |
| | WIND RESISTANCE RATING AS REQUIRED BY SEC. 107.2.1.2 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 5- SPECIFY ON ROOF UNDERLAYMENT PRODUCT APPROVAL |
| | SUBMITTED WHICH SPECIFIC UNDERLAYMENT IS GOING TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE WIND RESISTANCE |
| | RATING AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS TO |
| | FBC. |
| | |