| Plan Review Notes For Permit 13020827 |
| Permit Number |
13020827 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-28 10:50:47 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. SEE SHEET 31 OF THE NOA. THE ASSEMBLY SELECTED | | | REFERS TO GENERAL LIMITATION #9, NO ENHANCED FASTENING | | | ALLOWED. PLEASE SELECT ANOTHER ASSEMBLY WHICH EITHER | | | MEETS MINIMUM DESIGN PRESSURES FOR ZONES 2/3 OR REFERS | | | TO GENERAL LIMITATION #7, SEE SHEET 38. | | | | | | 2. ENHANCE FASTENING TO BE IN ACCORDANCE WITH RAS 117 | | | AND TO BE DONE BY AN ARCHITECT, ENGINEER, OR REGISTERED | | | ROOF CONSULTANT, SEE GENERAL LIMITATION #7 OF THE NOA. | | | | | | 3. INDICATE METHOD OF ATTACHMENT FOR THE TILE, FBC R | | | 301. IF AN ADHESIVE IS PROPOSED, PROVIDE PRODUCT | | | APPROVAL. | | | | | | 4. PROVIDE A COPY OF A VERIFIABLE CONTRACT FOR THIS | | | JOB, FBC 109. | | | | | | |
|