 5014 PINEWOOD AVE.
 RESIDENTIAL REPAIR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE SUBMITTED ELECTRIC SERVICE RISER IS MISSING THE
 GROUNDING CONDUCTOR, GROUNDING ELECTRODE, THE
 INTERSYSTEM BOND AND THE ELECTRICAL SERVICE WIRE SIZES.
 NEC 215.5, 250.94
  
 PROVIDE PANEL SCHEDULES FOR EACH UNIT. NEC 215.5
  
  