| Plan Review Notes For Permit 13020771 |
| Permit Number |
13020771 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-08 17:18:31 | 13010622 | | | 5014 PINEWOOD AVE. | | | RESIDENTIAL REPAIR | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | THE SUBMITTED ELECTRIC SERVICE RISER IS MISSING THE | | | GROUNDING CONDUCTOR, GROUNDING ELECTRODE, THE | | | INTERSYSTEM BOND AND THE ELECTRICAL SERVICE WIRE SIZES. | | | NEC 215.5, 250.94 | | | | | | PROVIDE PANEL SCHEDULES FOR EACH UNIT. NEC 215.5 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|