| Date |
Text |
| 2013-03-16 18:05:18 | 500 SOUTH AUSTRALIAN AVENUE - SUITE #501 |
| | PERMIT #13020768 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING |
| | SHALL BE PROHIBITED AND SHALL HAVE "NO SMOKING" SIGNS |
| | POSTED. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | SINCE THIS WILL BE A SINGLE TENANT, PROVIDE A LIFE |
| | SAFETY PLAN OF THE ENTIRE 5TH FLOOR SHOWING ALL EXIT |
| | STAIRS,OCCUPANCY TYPES, OCCUPANT LOADS, EXIT SIGNS, |
| | TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC. INDICATE |
| | WHICH FLOORS ARE DESIGNATED AS STAIRWELL RE-ENTRY |
| | FLOORS. |
| | |
| | DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS |
| | TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS |
| | PER SECTION 7.2.1.4.2 OF THE FLORIDA FIRE PREVENTION |
| | CODE: NFPA 101 - LIFE SAFETY CODE. |
| | |
| | EACH ELEVATOR LANDING AND LOBBY SHALL HAVE ACCESS TO AT |
| | LEAST ON EXIT. EXIT ACCESS SHALL NOT REQUIRE THE USE OF |
| | A KEY, TOOL, SPECIAL KNOWLEDGE, OR SPECIAL EFFORT. |
| | DOORS SEPARATING THE ELEVATOR LOBBY FROM THE EXIT |
| | ACCESS SHALL BE PERMITTED TO BE ELECTRONICALLY LOCKED |
| | IN ACCORDANCE WITH SECTION 7.2.1.6.3 (NFPA 101 - 2009 |
| | EDITION WITH FLORIDA AMENDMENTS). |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE |
| | ALARM SYSTEM. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |