Plan Review Notes
Plan Review Notes For Permit 13020690
Permit Number 13020690
Review Stop B
Sequence Number 2
Notes
Date Text
2013-03-04 11:30:57****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SEE THE INSTALLATION SCHEDULE:
  
 BLOCK SUBSTRATE (BOTTOM) TO USETHE SPACING FOR
 "SUBSTRATE BLOCK" ON SHEET 4 OF THE PRODUCT APPROVAL.
 9" DOES NOT COMPLY. PLEASE REVISE ANCHOR SPACING.
  
 COMMENT FROM PREVIOUS LIST:
  
 2. REVISE FLOOR PLAN TO SHOW ROOM DESIGNATION FOR THE
 EMERGENCY MEANS OF ESCAPE, FBC R310.4. THIS CANNOT BE
 LOCATED IN A ROOM WHICH CAN BE LOCKED.
  
 2ND REVIEW, ROOM DESIGNATIONS NOT PROVIDED. THE FRONT
 DOOR WAS HIGHLIGHTED; IS THIS AN INSWING OR OUTSWING
 DOOR? REVISE PLAN.
  
 IF THIS IS AN OUTSWING DOOR, THIS CANNOT OPERATE WITH
 THE SHUTTERS IN PLACE. THE TWO OTHER OPENINSG (9 AND
 10) DO NOT INCLUDE ROOM DESIGNATIONS. A TERRACE IS
 SHOWN; THIS APPEARS TO BE A PORCH, NOT A ROOM. IT IS
 NOT CLEAR WHETHER THE TERRACE IS LOCATED ADJACENT TO A
 ROOM WHICH CAN BE LOCKED.
  
  