| 2013-03-04 11:30:57 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. SEE THE INSTALLATION SCHEDULE: | | | | | | BLOCK SUBSTRATE (BOTTOM) TO USETHE SPACING FOR | | | "SUBSTRATE BLOCK" ON SHEET 4 OF THE PRODUCT APPROVAL. | | | 9" DOES NOT COMPLY. PLEASE REVISE ANCHOR SPACING. | | | | | | COMMENT FROM PREVIOUS LIST: | | | | | | 2. REVISE FLOOR PLAN TO SHOW ROOM DESIGNATION FOR THE | | | EMERGENCY MEANS OF ESCAPE, FBC R310.4. THIS CANNOT BE | | | LOCATED IN A ROOM WHICH CAN BE LOCKED. | | | | | | 2ND REVIEW, ROOM DESIGNATIONS NOT PROVIDED. THE FRONT | | | DOOR WAS HIGHLIGHTED; IS THIS AN INSWING OR OUTSWING | | | DOOR? REVISE PLAN. | | | | | | IF THIS IS AN OUTSWING DOOR, THIS CANNOT OPERATE WITH | | | THE SHUTTERS IN PLACE. THE TWO OTHER OPENINSG (9 AND | | | 10) DO NOT INCLUDE ROOM DESIGNATIONS. A TERRACE IS | | | SHOWN; THIS APPEARS TO BE A PORCH, NOT A ROOM. IT IS | | | NOT CLEAR WHETHER THE TERRACE IS LOCATED ADJACENT TO A | | | ROOM WHICH CAN BE LOCKED. | | | | | | |
|