| 2013-03-19 14:05:05 | IS DESIGN AS R-2 OR R-3? BOTH ARE INDICATED ON | | | DIFFERENT SHEETS | | | ELECTRIC SERVICE TO BE ON PROPERTY BEING SERVED OR | | | PROVIDE EVIDENCE OF LEGAL EASEMENT OR CONDO DOCS | | | NOTES CALL FOR THHN AND THWN, CHART CALLS FOR XHHW FOR | | | THE SERVICE CONDUCTORS | | | WHAT IS REVISION 1 AT GROUND ROD? CLOUDED AREA | | | SPECIFIC INSTRUCTIONS ARE PROVIDED FOR THE TERMINATION | | | OF ALUMINUM CONDUCTORS. PLEASE ENSURE THESE | | | INSTRUCTIONS ARE IN ACCORDANCE WITH THE CABLE | | | MANUFACTURERS INSTRUCTIONS | | | *INFORMATIONAL NOTE ON ELECTRIC - MUST MEET FAIR | | | HOUSING REQUIREMENTS* | | | MOUNTING HEIGHT AND REACH OF RECEPS, SWITCHES, AND | | | OTHER CONTROLS | | | |
|