Plan Review Notes
Plan Review Notes For Permit 13020667
Permit Number 13020667
Review Stop E
Sequence Number 1
Notes
Date Text
2013-03-19 14:05:05IS DESIGN AS R-2 OR R-3? BOTH ARE INDICATED ON
 DIFFERENT SHEETS
 ELECTRIC SERVICE TO BE ON PROPERTY BEING SERVED OR
 PROVIDE EVIDENCE OF LEGAL EASEMENT OR CONDO DOCS
 NOTES CALL FOR THHN AND THWN, CHART CALLS FOR XHHW FOR
 THE SERVICE CONDUCTORS
 WHAT IS REVISION 1 AT GROUND ROD? CLOUDED AREA
 SPECIFIC INSTRUCTIONS ARE PROVIDED FOR THE TERMINATION
 OF ALUMINUM CONDUCTORS. PLEASE ENSURE THESE
 INSTRUCTIONS ARE IN ACCORDANCE WITH THE CABLE
 MANUFACTURERS INSTRUCTIONS
 *INFORMATIONAL NOTE ON ELECTRIC - MUST MEET FAIR
 HOUSING REQUIREMENTS*
 MOUNTING HEIGHT AND REACH OF RECEPS, SWITCHES, AND
 OTHER CONTROLS
  