| Plan Review Notes For Permit 13020666 |
| Permit Number |
13020666 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-25 16:34:29 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. REVISE FLOOR PLAN TO INCLUDE EXISTING CONDITIONS | | | (TYPE OF WINDOW) AND OPENING SIZE FOR BEDROOMS, FBC | | | R310, FBC EB 604.1. THE CLEAR OPENING CANNOT BE REDUCED | | | BY MORE THAN 5%. NOTE THAT AWNING WINDOWS MAY HAVE AN | | | EMERGENCY ESCAPE PANEL. | | | | | | 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE | | | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM | | | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF). IF | | | SHUTTERS ARE INCLUDED IN THE SCOPE OF THIS PERMIT, | | | INCLUDE VALUE INCREASE. | | | | | | | | | |
|