 REVIEW COMMENTS - FIRE DEPARTMENT
 **RENEWAL OF EXPIRED SPRINKLER PERMIT**
  
 PROVIDE AN UPDATED FLOOR/CEILING PLAN TO MATCH THE
 CURRENT ARCHITECTURAL DESIGN.
  
 INDICATE THE EDITION OF NFPA 13 THAT THESE PLANS ARE IN
 COMPLIANCE WITH.
  
 CONFIRM NEW FIRE DEPARTMENT CONNECTION IS LOCATED
 WITHIN 150 FEET OF A FIRE HYDRANT.
  
 NO HAZARD INFORMATION (LIGHT, ORDINARY, ETC.) PROVIDED
 ON THE PLANS.
  
 FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING)
 INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR
 UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM
 SPRINKLER DISTANCE LOCATED BELOW THE STRUCTURE OR ROOF
 DECK (IF OBSTRUCTED CONSTRUCTION).
  
 NEW SPRINKLERS INSTALLED SHOULD BE QUICK-RESPONSE
 UNLESS THERE IS JUSTIFICATION TO INSTALL STANDARD
 RESPONSE SPRINKLERS.
  
 THE PLAN INDICATES AN INACCURATE SCALE OF 1/8"=1'-0".
  