| Plan Review Notes For Permit 13020649 |
| Permit Number |
13020649 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-02-26 15:47:18 | 425 24TH STREET | | | PERMIT #13020649 | | | MASTER #12030294 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | **RENEWAL OF EXPIRED SPRINKLER PERMIT** | | | | | | PROVIDE AN UPDATED FLOOR/CEILING PLAN TO MATCH THE | | | CURRENT ARCHITECTURAL DESIGN. | | | | | | INDICATE THE EDITION OF NFPA 13 THAT THESE PLANS ARE IN | | | COMPLIANCE WITH. | | | | | | CONFIRM NEW FIRE DEPARTMENT CONNECTION IS LOCATED | | | WITHIN 150 FEET OF A FIRE HYDRANT. | | | | | | NO HAZARD INFORMATION (LIGHT, ORDINARY, ETC.) PROVIDED | | | ON THE PLANS. | | | | | | FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING) | | | INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR | | | UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM | | | SPRINKLER DISTANCE LOCATED BELOW THE STRUCTURE OR ROOF | | | DECK (IF OBSTRUCTED CONSTRUCTION). | | | | | | NEW SPRINKLERS INSTALLED SHOULD BE QUICK-RESPONSE | | | UNLESS THERE IS JUSTIFICATION TO INSTALL STANDARD | | | RESPONSE SPRINKLERS. | | | | | | THE PLAN INDICATES AN INACCURATE SCALE OF 1/8"=1'-0". | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|