| 2013-05-24 11:07:50 | PLUMBING PLAN REVIEW |
| | PERMIT: 13020613 |
| | ADD: 6300 S DIXIE HWY # 101 & 102 |
| | CONT: ATANTIDA |
| | TEL: (561) 290-1472 |
| | |
| | 2010 FLORIDA BUILDING CODE- PLUMBING W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RDREVIEW |
| | DATE: MAY 24/ 2013 |
| | ACTION: DENIED |
| | |
| | NOTE: IT HS BEEN DETERMINED BY BUILDING & FIRE THAT |
| | THIS OCCUPANCY CLASSIFICATION IS A A3 ASSEMBLY |
| | OCCUPANCY, GYM WITHOUT SPECTATOR SEATING. OCCUPANT LOAD |
| | 490 SQ FT/ 15= 33 OCCUPANTS. |
| | 2010 FBC-EXISTING BUILDING 901.3.1 PARTIAL CHANGE OF |
| | OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN |
| | EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY |
| | CLASSIFICATION, SECTION 912 SHALL APPLY. |
| | 2010 EXST BLDG CODE 910.1 INCREASED DEMAND. WHERE THE |
| | OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN |
| | EXISTING BUILDING IS CHANGED SUCH THAT THE NEW |
| | OCCUPANCY IS SUBJECT TO INCREASED OR DIFFERENT PLUMBING |
| | FIXTURE REQUIREMENTS OR TO INCREASED WATER SUPPLY |
| | REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, PLUMBING, THE INTENT OF THE RESPECTIVE FLORIDA |
| | BUILDING CODE, PLUMBING PROVISIONS SHALL BE COMPLIED |
| | WITH FOR THE NEW OCCUPANCY. |
| | |
| | 1) THE 2010 FBC-P TABLE 403.1(1) MINIMUM REQUIRED |
| | FIXTURES WILL REQUIRE A HANDICAPPED RESTROOM FOR EACH |
| | SEX, A SERVICE SINK AND DRINKING FOUNTAIN, NOTE THE |
| | 2010 ACCESSIBILITY CODE REQUIRES A HIGH -LOW TYPE |
| | DRINKING FOUNTAIN TO MEET THE REQUIREMENTS OF : |
| | 602.4 SPOUT HEIGHT. |
| | SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. |
| | 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. |
| | SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 |
| | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | PLUMBING: |