| Plan Review Notes For Permit 13020613 |
| Permit Number |
13020613 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-04-09 08:51:08 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | PLUMBING REVIEW IS PENDING THE OUTCOME FOR THE | | | OCCUPANCY TYPE AND | | | OCCUPANT LOAD. PLEASE SEE BUILDING REVIEW COMMENTS. | | | | | | A BUSINESS OCCUPANCY WITH LESS THAN 3000 SQUARE FEET | | | WOULD ONLY REQUIRE ONE RESTROOM, AND WITH 15 OR LESS | | | OCCUPANTS WOULD NOT REQUIRE A HI/LOW DRINKING FOUNTAIN | | | (FBC | | | ACCESSIBILITY CODE 211.2) | | | FBC PLUMBING TABLE 403.1 | | | | | | ALSO, A YOGA STUDIO COULD BE AN ASSEMBLY OCCUPANCY. | | | THEN | | | SEPARATE FACILITIES ARE REQUIRED FOR EACH SEX, A HI/LOW | | | DRINKING FOUNTAIN (IF OCCUPANT LOAD IS OVER 15), AND A | | | SERVICE SINK. | | | FBC PLUMBING TABLE 403.1 AND 403.2 SEPARATE FACILITIES. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805?6692 | | | EMAIL [email protected] | | | FAX # 805?6676 |
|