| 2013-03-01 09:41:48 | BUILDING PLAN REVIEW |
| | PERMIT: 13020613 |
| | ADD: 6300 S DIXIE HWY |
| | CONT: ATLANTIDA |
| | TEL: (561)313-8126 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 03/01/2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1 NOTE # 2, UNDER THE HEADING INDICATES THE |
| | USE OF TABLE 302.1.1AND 2 HOUR FIRE WALL RATINGS, IN |
| | THE 2010 FBC-B THERE IS NO SUCH TABLE PLEASE UPDATE |
| | PLANS TO THE 2010 FBC-B. FIRE WALLS IS THE WRONG |
| | TERM,THEY ARE WALLS THAT SPLIT BUILDINGS INTO 2 |
| | BUILDINGS BECAUSE OF BEING TO LARGE FOR THE BUILDING |
| | TYPE DECLARED SEE 706. THE WALLS ARE TENAN SEPERATION |
| | WALLS ( FIRE PARTITIONS 709) OR OCCUPANCY SEPERATION |
| | WALLS. |
| | |
| | 2) SHEET A-1 NOTE # 3 UNDER THE HEADING INDICATES THE |
| | USE OF TABLE 302.1.1 AND 1 HOUR FIRE WALLS, IN THE 2010 |
| | FBC-B THERE IS NO SUCH TABLE PLEASE UPDATE PLANS TO THE |
| | 2010 FBC-B. |
| | |
| | 3) SHEET A-1 NOTE # 4 INDICATES A BUSINESS OCCUPANCY |
| | AND THE REFERENECE TO CODE SECTION 306 WHICH IS |
| | FACTORY? THEN UNDER THE HEADING NOTES OCCUPANCY TYPE ; |
| | MERCANTILE, THIS IS A YOGA SSTUDIO, PROVIDE THE AREA ON |
| | THE PLAN WHERE THE MERCANTILE AREA IS LOCATED. THIS |
| | TRUELY APPEARS TO BE A EXERCISE ROOM WITHOUT EQUIPMENT |
| | AND THE 15 SQ FT PER PERSON SHOULD BE USED PROVIDE WHAT |
| | AREA WILL BE USED FOR YOGA AND WHAT AREA WILL BE USED |
| | AS MERCANTILE FOR THE SALE OF GOODS, PROVIDE THE SQ FT |
| | PER AREA AND OCCUPANT LOADS FOR EACH AREA. DEPENDING ON |
| | THE SQ FOOTAGE THIS MAY BE A MIXED USE WILL THERE BE |
| | SEPERATION BETWEEN OCCUPANCIES OR NON SEPERATED USE OR |
| | ACCESSORY OCCUPANCIE? 508.4, 508.3 OR 508.2. |
| | |
| | 4) SHEET 1-A UNDER NOTES CLASSIFIES THIS BUILDING AS A |
| | TYPE III BUILDING UNDER THE 2001 AND EARLIER CODE A |
| | TYPE III BUILDING IDENTIFICATION WAS USED FOR A HEAVY |
| | TIMBER BUILDING, PLEASE USE THE NOMENCLATURE UNDER THE |
| | 2010 FBC-B TABLE 503.1 & TABLE 601. |
| | |
| | 5) THE WIND DESIGN CRITERIA IS NOT STATED TO THE 2010 |
| | FBC-B AND WIND CRITERIA FOR A CATEGORY II BUILDING V |
| | ULT 170 MPH, 3 SECOND GUST |
| | |
| | 6) UNDER THE WIND DESIGN CRITERIA THE EXPOSURE IS |
| | LISTED AS "M" ? 2010 FBC-B 1609. 4.2 SURFACE ROUGHNESS |
| | "C". |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |