| 2013-04-18 09:53:26 | 3620 SOUTH DIXIE HIGHWAY |
| | PERMIT #13020612 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****PROVISO - SUBMIT REVISION PROVIDING THE FOLLOWING |
| | INFORMATION***** |
| | |
| | REPEAT COMMENT: THE ADDRESS OF 3260 SOUTH DIXIE IS |
| | SHOWN ON THE PERMIT APPLICATION; HOWEVER, THIS LOCATION |
| | APPEARS TO BE 3620 SOUTH DIXIE HIGHWAY. |
| | |
| | REPEAT COMMENT: SMOKING SHALL BE PROHIBITED EXCEPT IN |
| | DESIGNATED EXTERIOR AREAS. ALL OTHER DEMOLITION OR |
| | CONSTRUCTION AREAS SHALL HAVE WEATHERPROOF "NO SMOKING" |
| | SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | REPEAT COMMENT: COMMERCIAL SPACE: PROVIDE PORTABLE FIRE |
| | EXTINGUISHERS. EXTINGUISHERS SHALL HAVE A MINIMUM |
| | RATING OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED |
| | FIRE EXTINGUISHER COMPANY. TRAVEL DISTANCE TO |
| | EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | RESPONSE COMMENT: IF THE WALL HAS A FIRE RESISTANCE |
| | RATING OF 2-HOURS, THEN THE DOOR OPENING TO BE |
| | PROTECTED NEEDS TO BE RATED FOR 90 MINUTES. TO INSTALL |
| | A 45-MINUTE RATED DOOR BECAUSE THE WALL IS OVERDESIGNED |
| | AS 2-HOURS IN LIEU OF 1-HOUR WILL BE VERY CONFUSING |
| | DURING INSPECTIONS. |
| | ORIGINAL COMMENT:SHEET A-1UA: DOORS SUCH AS #9 SHOULD |
| | HAVE A FIRE RESISTANCE RATING OF 90 MINUTES WHEN |
| | LOCATED WITHIN A 2-HOUR FIRE BARRIER. |
| | |
| | REVIEW #2 - NEW COMMENTS: |
| | SHEET FP-2: PROVIDE A SIAMESE FIRE DEPARTMENT |
| | CONNECTION WITH LOCKING KNOX CAPS. |
| | |