| Date |
Text |
| 2013-03-02 19:57:30 | 3620 SOUTH DIXIE HIGHWAY |
| | PERMIT #13020612 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE ADDRESS OF 3260 SOUTH DIXIE IS SHOWN ON THE PERMIT |
| | APPLICATION; HOWEVER, THIS LOCATION APPEARS TO BE 3620 |
| | SOUTH DIXIE HIGHWAY. |
| | |
| | NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION. |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | ALL CONSTRUCTION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | NO CIVIL DRAWINGS SUBMITTED SHOWING FIRE DEPARTMENT |
| | ACCESS ROADS, FIRE HYDRANT LOCATIONS AND UTILITIES. |
| | |
| | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE |
| | REQUIRED FOR A GENERAL BUILDING PERMIT WHEN THE SYSTEM |
| | DESIGN EXCEEDS 49 SPRINKLERS. AFTER THE BUILDING PERMIT |
| | HAS BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT |
| | SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | PROVIDE BUILDING AND UNIT ADDRESSES VISIBLE FROM THE |
| | STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND |
| | BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND |
| | SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION |
| | 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA |
| | 1). |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER "RF" |
| | (ROOF-FLOOR) DESIGNATION PER FLORIDA STATUTE 633.027 |
| | AND FLORIDA ADMINISTRATIVE CODE 69A-60.0081. |
| | |
| | SHEET A-1UA: DOORS SUCH AS #9 SHOULD HAVE A FIRE |
| | RESISTANCE RATING OF 90 MINUTES WHEN LOCATED WITHIN A |
| | 2-HOUR FIRE BARRIER. |
| | |
| | COMMERCIAL SPACE: PROVIDE PORTABLE FIRE EXTINGUISHERS. |
| | EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC |
| | AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER |
| | COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT |
| | EXCEED 75 FEET. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |