2013-03-11 16:58:10BUILDING PLAN REVIEW
 PERMIT: 13020612
 ADD: 3260 S DIXIE HWY (APPLICATION)
 PCN: 74-43-43-34-09-011-0230 = 3620 S DIXIE
 CONT: L&M HOMEBUILDERS, INC
 TEL: (561)436-0668
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 3/11/2013
 ACTION: DENIED
  
 1A) DISCREPANCIES: THE PERMIT APPLICATION APPEARS TO
 HAVE TRANSPOSED THE NUMBERS WITHIN THE ADDRESS, THEY
 WILL NEED TO BE CORRECTED. THE PCN NUMBER DOES TIE TO
 THE ADDRESS OF 3620 S DIXIE, PLEASE VERIFY.
  
 1B) MISSING FROM THE TITLE BLOCK IS THE ADDRESS FOR
 THIS BUILDING # 1.107.2.1.4 WEST PALM BCH
 ADMINISTRATIVE CODE 2010. 107.2.1.4 QUALITY OF BUILDING
 PLANS. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 2) I'VE SPOKE WITH THE B.O. ROBERT BROWN ABOUT THE
 ISSUE OF "FEE SIMPLE" TERM, AS IT IS EXPLAINED THIS IS
 TO BE REVIEWED AS A CONDO NOT A FEE SIMPLE PROJECT. THE
 TERM FEE SIMPLE IS ASSOCIATED WITH TOWN HOUSE
 CONSTRUCTION WHERE ALL ATTENDENT UTILITIES ONLY GO
 THROUGH THE SINGLE UNIT, NOT THROUGH ALL UNITS.
 TOWNHOUSE TYPE CONSTRUCTION HAS VERTICAL OWNERSHIP THAT
 DOES NOT OVER LAP FROM FLOOR TO FLOOR.
 F S 553.73
 2010 FBC-R CHAPTER 2
 DEFINITIONS
 TOWNHOUSE. A SINGLE-FAMILY DWELLING UNIT CONSTRUCTED IN
 A GROUP OF THREE OR MORE ATTACHED UNITS WITH PROPERTY
 LINES SEPARATING EACH UNIT IN WHICH EACH UNIT EXTENDS
 FROM FOUNDATION TO ROOF AND WITH A YARD OR PUBLIC WAY
 ON AT LEAST TWO SIDES.
 PUBLIC WAY. A STREET, ALLEY OR OTHER PARCEL OF LAND
 OPEN TO THE OUTSIDE AIR LEADING TO A STREET, THAT HAS
 BEEN DEEDED, DEDICATED OR OTHERWISE PERMANENTLY
 APPROPRIATED TO THE PUBLIC FOR PUBLIC USE AND WHICH HAS
 A CLEAR WIDTH AND HEIGHT OF NOT LESS THAN 10 FEET (3048
 MM).
  
 ARCHITECTURAL BOARD
 ?481.203DEFINITIONS.?AS USED IN THIS PART:
 ?(7)?TOWNHOUSE? IS A SINGLE-FAMILY DWELLING UNIT NOT
 EXCEEDING THREE STORIES IN HEIGHT WHICH IS CONSTRUCTED
 IN A SERIES OR GROUP OF ATTACHED UNITS WITH PROPERTY
 LINES SEPARATING SUCH UNITS. EACH TOWNHOUSE SHALL BE
 CONSIDERED A SEPARATE BUILDING AND SHALL BE SEPARATED
 FROM ADJOINING TOWNHOUSES BY THE USE OF SEPARATE
 EXTERIOR WALLS MEETING THE REQUIREMENTS FOR ZERO
 CLEARANCE FROM PROPERTY LINES AS REQUIRED BY THE TYPE
 OF CONSTRUCTION AND FIRE PROTECTION REQUIREMENTS; OR
 SHALL BE SEPARATED BY A PARTY WALL; OR MAY BE SEPARATED
 BY A SINGLE WALL MEETING THE FOLLOWING REQUIREMENTS:
 ?(A)SUCH WALL SHALL PROVIDE NOT LESS THAN 2 HOURS OF
 FIRE RESISTANCE. PLUMBING, PIPING, DUCTS, OR ELECTRICAL
 OR OTHER BUILDING SERVICES SHALL NOT BE INSTALLED
 WITHIN OR THROUGH THE 2-HOUR WALL UNLESS SUCH MATERIALS
 AND METHODS OF PENETRATION HAVE BEEN TESTED IN
 ACCORDANCE WITH THE STANDARD BUILDING CODE.
 ?(B)SUCH WALL SHALL EXTEND FROM THE FOUNDATION TO THE
 UNDERSIDE OF THE ROOF SHEATHING, AND THE UNDERSIDE OF
 THE ROOF SHALL HAVE AT LEAST 1 HOUR OF FIRE RESISTANCE
 FOR A WIDTH NOT LESS THAN 4 FEET ON EACH SIDE OF THE
 WALL.
 ?C)EACH DWELLING UNIT SHARING SUCH WALL SHALL BE
 DESIGNED AND CONSTRUCTED TO MAINTAIN ITS STRUCTURAL
 INTEGRITY INDEPENDENT OF THE UNIT ON THE OPPOSITE SIDE
 OF THE WALL.
  
 2A) COVER SHEET INDICATES EXTERIOR WALL RATINGS IN THE
 CONSIDERATION OF TABLE 601, BUT NO MENTION OF TABLE 602
 NOR TABLE 705.8 WHICH DEALS WITH AMOUNT OF OPENINGS AND
 OR THE PERCENTAGE OF OPENINGS IN A WALL AND FIRE
 SEPERATION REQUIREMENTS. THE THREE DIMENSIONAL SURVEYS
 DO NOT TAKE INTO CONSIDERATION THE REQUIREMENTS OF
 THESE CODE SECTIONS, AN EXAMPLE FOR LOT 1A WHICH HAS
 SIDE WINDOWS THE LOT LINE IS AT THE WALL LINE AS WELL
 AS THE FRONT DOOR WHICH SWINGS OUT OVER THE LOT LINE
 AND INTO TRACT "G", AGAIN THE CONCEPT IS A SINGLE
 BUILDING THAT WOULD BE APARTMENTS AND ONCE A
 CERTIFICATE OF OCCUPANCY IS ISSUED IT IS IN TURN
 RECORDED WITH THE STATE AS A DECLARATION OF
 CONDOMINIUM.
  
 2B) SURVEY FOR THE FIRST FLOOR FOR ALL UNITS ON THE
 FIRST FLOOR THE EXTERIOR DOORS SWING OUT OVER TRACT G
 AND THE DISTANCE TO THE PUBLIC RIGHT OF WAY IS ONLY
 2.84 FT. AWAY FROM THE BUILDING PLEASE REVIEW 2010
 FBC-B 3202.2 DOORS AND WINDOWS SHALL NOT OPEN INTO OR
 OVER THE RIGHT OF WAY.
  
 2C)THE COVER SHEET DOE INDICATE THIS BUILDING WILL BE
 FIRE SPPRINKLERED BUT NO FIRE SPRINKLER PLANS HAVE BEEN
 PROVIDED. PLEASE REVIEW THE 2010 FBC-B 903.2.8 &
 903.2.11.3.1.
  
 2D) THE FLOOR PLAN A-1UA IS REVERSED TO THE SURVEY, IS
 THERE GOING TO BE A REVERSE FLOOR PLAN FOR LAY OUT AND
 CONFIGURATIONS THAT MAY BE DIFFERENT THAN SHOWN?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET A-1UA THE DOOR SCHEDULE LIST DOOR # 2 AS A "C"
 LABELED DOOR, PLEASE REFER TO THE 2010 FBC-B 715.4
 WHICH LABELS OPENING PROTECTIVES IN HOURS OR PORTIONS
 OF HOURS.
  
 4) SHEET A-1UA THE WINDOW LABELED "D" IN THE WINDOW
 SCHEDULE DOES NOT MENTION THE REQUIREMENTS FOR SAFETY
 GLAZING IN ACCORDANCE WITH 2406.4(6).
  
 5) SHEET A-1UA THE WINDOW SCHEDULE WINDOW TYPE "B" IS
 MISSING THE PRODUCT APPROVAL FOR THIS TYPE OF UNIT.
 2010 FBC-B 1609.6.4.4.1.
  
 6) SHEET A-1UA INDICATES THE REMOVAL OF A BEARING
 TENANT SEPERATION WALL AS AN OPTION, PLEASE PROVIDE
 DETAILS AS TO HOW THE FLOOR /CEILING LOADS WILL BE
 TRANSFERRED TO THE FOUNDATION. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 7) SHEET A-1UA NOTES FOR ADAPTABLE UNITS (WITH
 ELEVATOR) DOES NOT REFER TO THE REQUIREMENT OF ALL
 INTERIOR DOORS ARE TO BE 32" CLEAR WIDTH NOR IS THERE
 ANY REFERENCE TO ACCESSIBLE ROUTES ONTO A BALCONY A 32"
 CLEAR WIDTH FOR THE SLIDDING GLASS DOORS OR THE
 REQUIREMENTS DO TO THE DIFFERENCE IN HEIGHT FROM
 INTERIOR FINISH FLOOR TO THE BALCONY DECK, FAIR
 HOUSING.
  
 8) SHEET A-1UA VERSES A1-UB THE STAIR TO THE SECOND
 FLOOR IN A1-UB DETAIL A DOES NOT PROVIDE IF THE SPACE
 UNDER THE STAIRS WILL BE USED FOR STORAGE? PLEASE SEE
 SHEET A-6 DETAIL 2 INDICATES THE STAIR BACKS UP TO A
 CBS WALL WHERE THE COMMON WALL TO THE STORAGE CLOSET IS
 FRAMED, IT APPEARS THERE IS A DESCEPANCY IN THE TYPE OF
 CONSTRUCTION?
 2010 FBC-B 1009.6.3.
  
 9) SHEET A-1UB IS MISSING THE FLOOR/ CEILING INSULATION
 BETWEEN THE GARAGE AND HABITAL SPACE ABOVE. 2010
 FBC-ENERGY 402.2.12
  
 10) SHEET A-1UB , DETAIL B/ A-7 INDICATES THE COMMON
 MASS WALL BETWEEN TENANT HABITABLE AREAS INDICATES A
 R-5.1 THE 2010 FBC ENERGY REQUIRES A R-6 VALUE FOR
 COMMON MASS WALLS 402.2.12 EXCEPTION.
  
 11) SHEET A7 & A8 BOTH PROVIDE ROOF SECTIONS BUT
 NEITHER DETAIL PROVIDES COMPLIANCE WITH 2010 FBC-B
 1203.2 ATTIC SPACES. WITH 50 PERCENT OF THE REQUIRED
 VENTILATING AREA PROVIDED BY VENTILATORS LOCATED IN THE
 UPPER PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3
 FEET (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE
 BALANCE OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR
 CORNICE VENTS.
  
 12) MISSING SOILS REPORT FOR THE SAME MINIMUM SOILS
 BEARING CAPACITY. 2010 FBC-B 1803.2 INVESTIGATIONS
 REQUIRED. GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTIONS 1803.3 THROUGH
 1803.5. 1803.6 REPORTING.
 WHERE GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A
 WRITTEN REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED
 TO THE BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED
 AGENT AT THE TIME OF PERMIT APPLICATION. SEE 1803.6
 (1-10).
  
 13) SHEET S-2 IS MISSING PART OF THE FLOOR TRUSS SYSTEM
 THAT IS IN THE CORRIDOR FIRST FLOOR AND ABOVE THE AREA
 THAT MAKES UP PART OF THE DINING ROOM FLOOR. THIS AREA
 IS NO DEPICTED IN THE LAYOUT SHEET S-2 WHERE DOES THE
 GIRDER END, OR WHAT DOES IT SIT ON ? IT APPEARS THERE
 IS EITHER A POST OR COLUMN AT THE END OF THE GIRDER?
 107.2.1.3 ADDITIONAL INFORMATION.
  
 14) SHEET S-2 (LEDGERS) & S-4 TYPICAL TENANT SEPERATION
 WALL LEDGER TYPE A IS DEPICTED AT BEING LOCATED AT
 EITHER THE FLOOR SHEATHING OR ROOF SHEATHING LINE BUT
 THE PLANS DO NOT INDICATE WHAT WILL HOLD UP THE DRYWALL
 CEILING TO ATTACH TO OR HOW THE BOTTOM LEDGER WILL BE
 FASTEENED TO THE CMU WALL. 107.2.1.3. ADDITIONAL
 INFORMATION.
  
 15) SHEET S-2 THE FLOOR FRAMING PLAN INDICATES FILLED
 CELL CMU BUT THE COLUMNS ON THE FRONT OF THE BUILDING
 ARE NOT IDENTIFIED, THEY ARE ON THE FIRST FLOOR, BUT
 NOT THE SECOND FLOOR?
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 16) SHEET A-7 INDICATES THE USE OF A PEEL & STICK
 UNDERLAYMENT, NO PRODUCT APPROVAL WAS SUBMITTED IN THIS
 REVIEW CYCLE. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 PLEASE NOTE THE PLANS INDICATED THE USE OF PEEL & STICK
 TO DIRECT DECK, PLEASE CIRCLE WHICH SUB-SYSTEM WILL BE
 INSTALLED, IF IT IS A MIAMI-DADE NOA PLEASE ALSSO READ
 THE LIMITATIONS FOR DIRECT DECK APPLICATION. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS: (D) ROOFING
 PRODUCTS AND ASSEMBLIES, INCLUDING SUB-SYSTEMS.
  
 17) ENTEGRA ROOF TILE, DOES NOT HAVE THE DESIGNER OF
 RECORD SHOP DRAWING STAMP ON THEM, PLEASE CIRCLE WHICH
 TYPE OF APPLICATION WILL BE USED IN THE APPLICATION OF
 THIS PRODUCT, IF FOAM OR A MORTAR SET SYSTEM IS TO BE
 USED IN THE INSTALATION THEN PRODUCT APPROVALS WILL
 ALSO NEED TO BE SUBMITTED, HIGHLIGHT THE APPLICATION TO
 BE USED IN THE INSTALATION, AND REVIEWED BY THE
 DESIGNER OF RECORD. RULE 9N-3 (31) (D), & 107.2.4.1.
  
 18) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved