| 2013-03-14 11:02:41 | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS. | | | NEC 422.52 | | | | | | WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES | | | A SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT | | | GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT | | | GROUND. NEC 517.13 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|