| 2013-03-12 13:59:51 | BUILDING PLAN REVIEW |
| | PERMIT: 13020602 |
| | ADD: 2555 PALM BCH LAKES # 100 |
| | CONT: FISHER CONTRACTING |
| | TEL: (561)691-4716 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 3/12/2013 |
| | ACTION: DENIED |
| | |
| | 1) BUILDING DATA INDICATES THIS TO BE A TYPE III |
| | BUILDING, PLEASE REVIEW THE 2010 FBC-B TABLE 503 FOR A |
| | 15 STORY BUILDING IT HAS TO BE BUILDING TYPE IA. |
| | |
| | 2) PLEASE PROVIDE ADDITIONAL DATA FOR THE WATER CURTAIN |
| | IN THE MAIN LOBBY, WATER CURTAINS ARE TO BE INSTALLED |
| | IN AN ATRIUM MEETING ALL THE REQUIEMENTS OF AN ATRIUM |
| | WITH SMOKE CONTROL PER 2010 FBC-B909. EXIST BLDG CODE |
| | 704.2.1 FIRE PROTECTION SEE SECTION 403 OF THE FBC-B. |
| | 403.6 SMOKE REMOVAL SHALL BE PROVIDED IN ACCORDANCE |
| | WITH 909 FBC-B. |
| | |
| | 3) SHEET A-3 INDICATES A FIRE SPRAY PLAN, A NOTE THAT |
| | INDICATES FIRE SPRAY THE ENTIRE ROOF STRUCTURES AS |
| | SHOWN , AND THE PLAN IS THE INTERIOR SPACE OF UNIT # |
| | 100. ADDITIONAL INFORMATION REQUIRED, 107.2.1.3. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |