Plan Review Notes
Plan Review Notes For Permit 13020565
Permit Number 13020565
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-02-23 14:30:44435 SOUTHERN BOULEVARD
 PERMIT #13020565
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - REVISION MAY NEED TO BE SUBMITTED*****
  
 DUCTS CONVEYING HAZARDOUS EXHAUSTS (COMBUSTIBLE DUST)
 SHALL BE INTERNALLY PROTECTED BY AUTOMATIC SPRINKLERS.
 SPRINKLERS SHALL BE PROVIDED IN DUCTS WITH A
 CROSS-SECTIONAL DIAMETER OF 10-INCHES OR GREATER.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING)
 INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR
 UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM
 SPRINKLER DISTANCE LOCATED BELOW THE STRUCTURE OR ROOF
 DECK (IF OBSTRUCTED CONSTRUCTION).
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF
 7'-6" TO THE FRONT AND SIDES AND 4' TO THE BACKSIDE.
  
 SHEET FP-2: THE FIRE DEPARTMENT CONNECTION IS
 INCORRECTLY LOCATED UPSTREAM OF THE BACKFLOW PREVENTER.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730