Plan Review Notes
Plan Review Notes For Permit 13020554
Permit Number 13020554
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-03-18 13:23:586651 NORTH JOG ROAD - TIPPING BUILDING
 TRACKING #13020554
 PERMIT #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET FP-100: THE TIPPING BUILDING IS APPROXIMATELY 150
 FEET WIDE AND THE NOTIFICATION APPLIANCES INDICATE A
 CANDELA RATING OF 135 CD. NFPA 72 (2010 ED.) TABLE
 18.5.43.1(A) APPEARS TO INDICATE THAT WALL MOUNTED 135
 CD APPLIANCES CAN COVER A ROOM WIDTH OF 110 FEET WHICH
 WILL RESULT IN INADEQUATE NOTIFICATION AT THE MIDPOINT
 OF THE TIPPING BUILDING.
  
 SHEET FP-113: PER NFPA 13 SECTION 8.16.1.2.1 "IN
 PORTIONS OF SYSTEMS WHERE ALL COMPONENTS ARE NOT LISTED
 FOR PRESSURE GREATER THAN 175 PSI AND THE POTENTIAL
 EXISTS FOR NORMAL (NONFIRE CONDITION) WATER PRESSURE IN
 EXCESS OF 175 PSI, A LISTED PRESSURE-REDUCING VALVE
 SHALL BE INSTALLED AND SET FOR AN OUTLET PRESSURE NOT
 EXCEEDING 165 PSI AT THE MAXIMUM INLET PRESSURE."
  
 SHEET FP-113: PROVIDE EXTERIOR PIV OR RISER WALL PIVS.
  
 SHEET FP-113: NFPA 850 ( FIRE PROTECTION FOR ELECTRIC
 GENERATING PLANTS & HIGH VOLTAGE DC CONVERTER STATIONS)
 SECTION 9.1.5.6 INDICATES, "AUTOMATIC SPRINKLERS SHOULD
 BE CORROSION RESISTANT TO WITHSTAND CORROSION FROM
 PRODUCTS OF COMBUSTION FROM COMBUSTION ENGINE-DRIVEN
 FRONT END LOADERS AND FROM TRASH TRUCKS."
  
 SHEET FP-113: NFPA 850 (FIRE PROTECTION FOR ELECTRIC
 GENERATING PLANTS & HIGH VOLTAGE DC CONVERTER STATIONS)
 SECTION 9.3.3.1 INDICATES, "THE TIPPING/RECEIVING
 BUILDING SHOULD BE PROVIDED WITH HIGH TEMPERATURE
 SPRINKLERS 250F TO 300F.
  
 SHEET FP-113: COULD NOT LOCATE HYDRAULIC CALCULATIONS.
 PLEASE SUBMIT.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  