| 2013-03-18 13:23:58 | 6651 NORTH JOG ROAD - TIPPING BUILDING |
| | TRACKING #13020554 |
| | PERMIT #12040748 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET FP-100: THE TIPPING BUILDING IS APPROXIMATELY 150 |
| | FEET WIDE AND THE NOTIFICATION APPLIANCES INDICATE A |
| | CANDELA RATING OF 135 CD. NFPA 72 (2010 ED.) TABLE |
| | 18.5.43.1(A) APPEARS TO INDICATE THAT WALL MOUNTED 135 |
| | CD APPLIANCES CAN COVER A ROOM WIDTH OF 110 FEET WHICH |
| | WILL RESULT IN INADEQUATE NOTIFICATION AT THE MIDPOINT |
| | OF THE TIPPING BUILDING. |
| | |
| | SHEET FP-113: PER NFPA 13 SECTION 8.16.1.2.1 "IN |
| | PORTIONS OF SYSTEMS WHERE ALL COMPONENTS ARE NOT LISTED |
| | FOR PRESSURE GREATER THAN 175 PSI AND THE POTENTIAL |
| | EXISTS FOR NORMAL (NONFIRE CONDITION) WATER PRESSURE IN |
| | EXCESS OF 175 PSI, A LISTED PRESSURE-REDUCING VALVE |
| | SHALL BE INSTALLED AND SET FOR AN OUTLET PRESSURE NOT |
| | EXCEEDING 165 PSI AT THE MAXIMUM INLET PRESSURE." |
| | |
| | SHEET FP-113: PROVIDE EXTERIOR PIV OR RISER WALL PIVS. |
| | |
| | SHEET FP-113: NFPA 850 ( FIRE PROTECTION FOR ELECTRIC |
| | GENERATING PLANTS & HIGH VOLTAGE DC CONVERTER STATIONS) |
| | SECTION 9.1.5.6 INDICATES, "AUTOMATIC SPRINKLERS SHOULD |
| | BE CORROSION RESISTANT TO WITHSTAND CORROSION FROM |
| | PRODUCTS OF COMBUSTION FROM COMBUSTION ENGINE-DRIVEN |
| | FRONT END LOADERS AND FROM TRASH TRUCKS." |
| | |
| | SHEET FP-113: NFPA 850 (FIRE PROTECTION FOR ELECTRIC |
| | GENERATING PLANTS & HIGH VOLTAGE DC CONVERTER STATIONS) |
| | SECTION 9.3.3.1 INDICATES, "THE TIPPING/RECEIVING |
| | BUILDING SHOULD BE PROVIDED WITH HIGH TEMPERATURE |
| | SPRINKLERS 250F TO 300F. |
| | |
| | SHEET FP-113: COULD NOT LOCATE HYDRAULIC CALCULATIONS. |
| | PLEASE SUBMIT. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |