 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENTS:
 REPEAT COMMENT: THE PERMIT APPLICATION ADDRESS (6801 N
 JOG ROAD) DOES NOT MATCH THE CORRECT ADDRESS (6610 N
 JOG ROAD) INDICATED ON THE PLANS.
  
 REPEAT COMMENT: THE PLANS INDICATE THE DRAWING SCALE TO
 BE 1/8"=1'-0"; HOWEVER, THE ACTUAL SCALE APPEARS TO BE
 3/16"=1'-0". PLANS STILL INDICATE 1/8"=1'-0.
  
 REPEAT COMMENT: THE PLANS INCORRECTLY INDICATE TWO
 HYDRAULIC NODES AS "A3" AND THESE FLOWING NODES CANNOT
 BE LOCATED IN THE HYDRAULIC CALCULATIONS. ALSO THE
 HYDRAULIC CALCULATIONS INDICATE NODE 4 TO BE A FLOWING
 NODE WHICH IS INACCURATE. NODES B9, B10 AND 11 ARE NOT
 SHOWN ON THE PLANS.
  
 NEW COMMENT: THE FIRE DEPARTMENT CONNECTION SHOULD NO
 LONGER BE SHOWN ADJACENT TO THE BACKFLOW PREVENTER AS
 THE UNDERGROUND CONTRACTOR HAS RELOCATED THIS DEVICE.
  
  
 FIELD NOTES:
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 IN ADDITION TO TAMPER SWITCHES, PROVIDE CHAIN WITH LOCK
 FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  