| 2013-06-20 14:29:28 | 6801 NORTH JOG ROAD |
| | PERMIT #13020518 |
| | (SEE ALSO PERMIT #13020494) |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FAIL COMMENTS: |
| | REPEAT COMMENT: THE PERMIT APPLICATION ADDRESS (6801 N |
| | JOG ROAD) DOES NOT MATCH THE CORRECT ADDRESS (6610 N |
| | JOG ROAD) INDICATED ON THE PLANS. |
| | |
| | REPEAT COMMENT: THE PLANS INDICATE THE DRAWING SCALE TO |
| | BE 1/8"=1'-0"; HOWEVER, THE ACTUAL SCALE APPEARS TO BE |
| | 3/16"=1'-0". PLANS STILL INDICATE 1/8"=1'-0. |
| | |
| | REPEAT COMMENT: THE PLANS INCORRECTLY INDICATE TWO |
| | HYDRAULIC NODES AS "A3" AND THESE FLOWING NODES CANNOT |
| | BE LOCATED IN THE HYDRAULIC CALCULATIONS. ALSO THE |
| | HYDRAULIC CALCULATIONS INDICATE NODE 4 TO BE A FLOWING |
| | NODE WHICH IS INACCURATE. NODES B9, B10 AND 11 ARE NOT |
| | SHOWN ON THE PLANS. |
| | |
| | NEW COMMENT: THE FIRE DEPARTMENT CONNECTION SHOULD NO |
| | LONGER BE SHOWN ADJACENT TO THE BACKFLOW PREVENTER AS |
| | THE UNDERGROUND CONTRACTOR HAS RELOCATED THIS DEVICE. |
| | |
| | |
| | FIELD NOTES: |
| | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED |
| | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. |
| | |
| | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE |
| | DEPARTMENT CONNECTION. |
| | |
| | IN ADDITION TO TAMPER SWITCHES, PROVIDE CHAIN WITH LOCK |
| | FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN |
| | POSITION. |
| | |