| 2013-02-23 12:51:47 | 6801 (6610) NORTH JOG ROAD |
| | PERMIT #13020518 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PERMIT APPLICATION ADDRESS DOES NOT MATCH THE |
| | CORRECT ADDRESS INDICATED ON THE PLANS. |
| | |
| | THE PLANS INDICATE THE DRAWING SCALE TO BE 1/8"=1'-0"; |
| | HOWEVER, THE ACTUAL SCALE APPEARS TO BE 3/16"=1'-0". |
| | |
| | THE PLANS INCORRECTLY INDICATE TWO HYDRAULIC NODES AS |
| | "A3." ALSO, THESE FLOWING NODES CANNOT BE LOCATED IN |
| | THE HYDRAULIC CALCULATIONS. |
| | |
| | PROVIDE A RISER DETAIL(S). |
| | |
| | FIRE DEPARTMENT CONNECTION SHALL BE LOCATED WITHIN 150 |
| | FEET OF A FIRE HYDRANT. |
| | |
| | PLANS DO NOT INDICATE WHAT PIPING MATERIAL WILL BE USED |
| | FOR THE UNDERGROUND INSTALLATION. |
| | |
| | PLANS DO NOT INDICATE THE PIPING MATERIAL OF THE |
| | EXISTING 4" WATER MAIN. |
| | |
| | THE PLANS ARE NOT CLEAR HOW THE PIPING IS BEING ROUTED |
| | FROM THE "SUB CONTRACTOR" TRAILER TO THE "MATERIAL |
| | RECEIVING" TRAILER. |
| | |
| | SUBMIT PRODUCT DATA FOR THE CPVC PIPING AND BACKFLOW |
| | PREVENTER TO BE INSTALLED. PROVIDE DOCUMENTATION |
| | SUPPORTING THE USE OF EXPOSED CPVC PIPING. |
| | |
| | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED |
| | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. |
| | |
| | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE |
| | DEPARTMENT CONNECTION. |
| | |
| | IN ADDITION TO TAMPER SWITCHES, PROVIDE CHAIN WITH LOCK |
| | FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN |
| | POSITION. |
| | |