2013-02-23 12:51:476801 (6610) NORTH JOG ROAD
 PERMIT #13020518
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION ADDRESS DOES NOT MATCH THE
 CORRECT ADDRESS INDICATED ON THE PLANS.
  
 THE PLANS INDICATE THE DRAWING SCALE TO BE 1/8"=1'-0";
 HOWEVER, THE ACTUAL SCALE APPEARS TO BE 3/16"=1'-0".
  
 THE PLANS INCORRECTLY INDICATE TWO HYDRAULIC NODES AS
 "A3." ALSO, THESE FLOWING NODES CANNOT BE LOCATED IN
 THE HYDRAULIC CALCULATIONS.
  
 PROVIDE A RISER DETAIL(S).
  
 FIRE DEPARTMENT CONNECTION SHALL BE LOCATED WITHIN 150
 FEET OF A FIRE HYDRANT.
  
 PLANS DO NOT INDICATE WHAT PIPING MATERIAL WILL BE USED
 FOR THE UNDERGROUND INSTALLATION.
  
 PLANS DO NOT INDICATE THE PIPING MATERIAL OF THE
 EXISTING 4" WATER MAIN.
  
 THE PLANS ARE NOT CLEAR HOW THE PIPING IS BEING ROUTED
 FROM THE "SUB CONTRACTOR" TRAILER TO THE "MATERIAL
 RECEIVING" TRAILER.
  
 SUBMIT PRODUCT DATA FOR THE CPVC PIPING AND BACKFLOW
 PREVENTER TO BE INSTALLED. PROVIDE DOCUMENTATION
 SUPPORTING THE USE OF EXPOSED CPVC PIPING.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 IN ADDITION TO TAMPER SWITCHES, PROVIDE CHAIN WITH LOCK
 FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  